UniPOS
Fire Control Panel FS5100
Instruction Manual
Page 6
Revision 7/06.12
Of 47
FIRE CONDITION STAGE I – upon activation of automatic fire detector the fire control panel
enters Fire condition until the defined time expires. The common and local light indicators, local sound
signaling and a text message displayed on the LCD display indicate the phase.
FIRE CONDITION STAGE II – the fire control panel enters Fire condition stage II when: a) the
time for
Fire condition stage I
has expired or b) upon activation of a manual call point. The common
and local light indicators, local sound signaling and a text message displayed on the LCD display
indicate the phase.
FIRE DETECTOR REMOVED –
non-fatal fault condition
due to removed fire detector in a
line
. To
use this function, the fire detectors shall be connected as in Appendix 7 a.
FUNCTION “LOGICAL AND” OF TWO LINES – function that allows the fire control panel to enter
Fire condition stage I
upon simultaneous activation of automatic fire detectors in two
lines
. (see
section 6.3).
GROUNDS –
non-fatal fault condition
, due to leakage to a grounded wire.
GROUP ADDRESSING – fire control panel’s ability to make difference between activation of
automatic fire detector and manual call point, which are in one and the same
fire alarm line
. For this
purpose the manual call points’ current consumption value shall exceed the threshold value for
Fire
condition stage II.
INSPECTION TIME – period of time added to the remaining time, before the system proceeds
from
Fire condition stage I
to
Fire condition stage II
, when button
is pressed. Usually, this
period of time is long enough for the authorized personnel to check up the indicated premises. The
inspection time is user defined and is equal for all
fire alarm lines
. Light indicators show adding a
period of time for inspection.
INTERRUPTED LINE OR CONTROLLABLE OUTPUT –
non-fatal fault condition
due to current
value in a line or in controllable output lower than the threshold value. The user shall define the
threshold value separately for each line.
LINE IN TEST –
line
set
in Test condition by the user. The line is powered and reset (the power is
cut off for 3 s) periodically every 64 s. The events registered in a line in Test condition are not saved
in the archive and do not trigger the associated outputs or the light and sound signalling. The
indication for a line in Test condition is common light indication.
LINE STATUS OR CONTROLLABLE OUTPUT STATUS – current status of a
line
or a
controllable output
: normal status; fire conditions stage I or II (for a line only); fault condition and its
type.
LOCAL SOUNDER - sounder built-in the fire control panel.
LOW BATTERY –
fatal fault condition
due to full discharge of the backup batteries upon
interrupted power supply.
NON-FATAL FAULT CONDITION – fault condition that allows the fire control panel to continue
operation. The indication is common light indication, local sound indication and text messages on the
LCD display.
PRE-FIRE CONDITION – condition of the fire control panel using the function
Logical AND of two
lines
to provide control over simultaneous response of automatic fire detectors in the
lines
. (see
section 6.3).
PROCEEDING FROM FIRE CONDITION STAGE I TO FIRE CONDITION STAGE II – the time is
user defined for each
fire alarm line
separately. During the phase
Fire condition stage I
the remaining