UniPOS
Fire Control Panel FS5100
Instruction Manual
Page 31
Revision 7/06.12
Of 47
14.2.5. Function
Adjustment of relay outputs
Activate the function from the screen:
When the function is active the following command screen
appears:
where
Х
can adopt 0 (the relay output will not operate) or 1 (the relay output will operate). The left
position corresponds to Relay output 1. Press button
to activate the selected relay outputs and
keep them active by holding the button down. Deactivate the function by pressing the button
.
14.2.6. Function
Default parameters
Select the function from the screen:
Upon activation of the function the following default parameters are saved in the energy
independent memory of the fire control panel
−
Line parameters:
♦
Number of reviews - 2;
♦
Check up for a removed fire detector - activated;
♦
Period for transition from Fire condition stage I to Fire condition stage II - 120s;
♦
Current threshold above which Fire condition stage I in a line is detected - 12mA;
♦
Current threshold above which Fire condition stage II in a line is detected - 40mA;
♦
Current threshold above which Short circuit in a line is detected - 70mA;
♦
Current threshold below which Break in a line is detected - 3mA;
♦
Logical AND of a line – not set;
♦
Controllable outputs upon Fire condition stage I in a line – will not operate;
♦
Controllable outputs upon Fire condition stage II in a line – will not operate;
♦
Relay outputs upon Fire condition stage I in a line – will not operate;
♦
Relay outputs upon Fire condition stage II in a line – will not operate;
−
Fire control panel parameters:
♦
Inspection time - 120s;
♦
Interface number - 1234;
♦
Baud rate - 9600bd;
♦
Modem – no modem;
♦
Language - English
−
Lines in test condition – no such lines;
−
Disabled lines – no such lines;
−
Disabled controllable outputs – no such outputs.
14.2.7. Function
Clear archive
Select the function from the screen:
Use it to delete events information saved in the energy independent memory of the fire control
panel.
The activated function displays the following screen:
The counter of fire conditions is not deleted here. It can be zeroed in a special mode only (Access
level 4).
Clear Archive
≥≥
Clear Archive
Default
Rl Adj
ХХХХХ
Rl Adj