UniPOS
Fire Control Panel FS5100
Instruction Manual
Page 36
Revision 7/06.12
Of 47
Тable
4
Trouble
Indication
Troubleshooting
System error
Indicators
and
illuminate in
steady yellow light; the local sounder
releases continuous signal; the message
Syst. Error
is displayed;
The trouble shall be fixed in
Service department
Circuit boards conflict
Indicator
flashes in yellow light,
indicator
illuminates in continuous
yellow light; the message
Boards Conflict
appears on the screen
Enter Set Up Mode. Exit the
mode and if the problem
persists, it shall be fixed in
Service department
Low backup batteries
due to interrupted
mains power supply
The local sounder releases
discontinuous signal (1s sound, 3s
pause); the message
Batt Low
appears
on the screen; the backlight of the
display is off
Restore the mains power supply
or replace the backup batteries
Fault in a line
Indicator
flashes in yellow light;
the local sounder releases discontinuous
signal; the message
Flt: Ln
appears on
the screen
- Eliminate the fault (short
circuit, interrupted power supply
or removed fire detector);
- In Fault condition: Removed
FD check for short circuit in a
component to a ground wire
(see
Fault condition: Short
circuit to ground wire
)
Fault in a controllable
output
Indicators
and
; illuminate in
steady yellow light; the local sounder
releases discontinuous signal; the
message
Flt: cO
appears on the display
- Eliminate the fault (short circuit
or interruption) in the fire alarm
line of the controllable output or
executive device;
- Upon
Fault condition
:
Interruption
check for short
circuit in component of the
controllable output to ground
wire (see
Fault condition: Short
circuit to ground wire
)
Fault in mains power
supply
Indicators
and
illuminate in
steady yellow light; the local sounder
releases discontinuous signal; the
message
No 220V
appears on the
screen
- Restore the mains power
supply;
- Substitute Fuse 1 – 4A with a
mains fuse
Fault in backup battery
supply
Indicators
and
illuminate in
steady yellow light, the local sounder
releases discontinuous signal; the
message
Flt: Battery
appears on the
dipslay
- Place or replace the backup
batteries;
- Replace the burnt fuse Fs 2 –
4A
Fault in power supply
to external devices
Indicator
flashes in yellow light; the
local sounder releases discontinuous
signal; the message
Flt
:
Uuser
appears
on the display
Eliminate overload of power
supply to external devices