UniPOS
Fire Control Panel FS5100
Instruction Manual
Page 23
Revision 7/06.12
Of 47
13.2.2.
Function
Fire alarm lines test
The function is activated from the screen
When the function is active, the following command screen
appears, where X can be 0 (fire alarm line not in test condition) or
1 (fire alarm line in test condition):
The first position corresponds to Line 1, the last position corresponds to Line 8.
Press the button
to move the cursor one position to the right; when the last (eighth fire
alarm line) position is reached the cursor moves to position one (first fire alarm line)
Press the button
to alternatively change the value from 0 to 1 and vice versa, of the
position selected by the cursor. The changes (fire alarm line set to test condition or out of test
condition) become valid when button
is pressed; the function is not deactivated then. To
deactivate it press
or press once again
.
Press
to activate all outputs (controllable and relay outputs), which operate in Fire
Condition stage I or II in all lines in test condition. The outputs are active until the button is being
pressed. The button operates upon activated function
Fire alarm lines test
and upon absence of
unaccepted changes, i.e. if:
−
no changes are made after the function has been activated or
−
changes have been entered by a single pressing of
; the function is not deactivated.
13.2.3. Function
Disable fire alarm lines
The function is activated from the screen
When the function is active, the following command screen
appears, where X can be 0 (fire alarm line is enabled) or 1 (fire
alarm line is disabled):
The first position corresponds to Line 1, the last position corresponds to Line 8.
13.2.4. Function
Disable controllable outputs
The function is activated from the screen:
When the function is active, the following command screen
appears, where X can be 0 (controllable output is enabled) or 1
(controllable output is disabled):
The left position corresponds to Controllabel output 1.
13.2.5. Menu
Current in fire alarm lines
Select he menu from the screen:
Information screens for current in lines appears; N is the
number of the selected fire alarm line, the current is in mA:
Crr LnN
CCC mA
Crr Ln
Dsbl cO
ХХ
Dsbl cO
Dsbl Ln
ХХХХХХХХ
Dsbl Ln
Test Ln
ХХХХХХХХ
Test Ln