UniPOS
Fire Control Panel FS5100
Instruction Manual
Page 37
Revision 7/06.12
Of 47
Тable
4 - Continue
Trouble
Indication
Troubleshooting
Short circuit to ground
wire
Indicator
flashes in yellow light; the
local sounder releases discontinuous
signal; the message
Flt: Earth
appears
on the display
Eliminate the short circuit
Fault in internal power
supply
Indicator
flashes in yellow light; the
local sounder releases discontinuous
signal; the message
Flt: Uintrn
appears
on the display
The fault shall be fixed in
Service department
Fault in charger
Indicators
and
; illuminate in
steady yellow light; the local sounder
releases discontinuous signal; the
message
Flt: Charger
appears on the
screen
The fault shall be fixed in
Service department
22. Conditions of operation, storage and transportation
22.1. Operation and storage
The fire control panel shall operate and be kept in closed premises, under the following
conditions:
22.1.1. Temperature
−
storage
- from +
5 tо +35
°
C
−
transportation
- from -
10 tо
+50
°
C
−
operation
- from -5
°
С tо +40
°
С
22.1.2. Relative humidity
−
storage
- up to 80
%
−
operation
- up to 93
%
22.2. Transportation
The fire control panel shall be transported by vehicles, in factory packing, in the above stated
environmental conditions and at sinusoidal vibrations with accelecartion amplitude not more than
4,9m/s
2
in frequency range 10 to 150Hz.
23. Warranty
The producer guarantees compliance of the unit with EN 54-2:
1997/ А1: 2006/ АС: 2009,
EN 54-
4:
1997/ А2: 2006/ АС
2009. The warrant period is 18 months from the date of the purchase,
providing that
−
The conditions of storage and transportation have been observed;
−
The startup has been done by authorized personnel only
−
The requirements for operation stated herein have been observed.