UniPOS
Fire Control Panel FS5100
Instruction Manual
Page 10
Revision 7/06.12
Of 47
6. General information
6.1. Access levels
There are 4 levels of access to the variable indications and control functions of FS5100.
6.1.1. Access level 1
All persons who would presumably find out and react to alarm for fault condition or fire condition
have access to level 1.
The following features are accessible:
−
Displaying suppressed messages for Fire condition, Fault condition and Disabled lines
(see sections 8, 10 and 11);
−
Entering inspection time period (see section 8);
−
Forced proceeding from phase Fire condition stage I to phase Fire condition stage II (see
section 8);
−
Displaying the status of the lines and of the controllable outputs (see section 13).
All light indicators are visible.
6.1.2. Access level 2
The personnel in charge for the fire protection have access to level 2; they shall be authorized
and trained to operate the fire control panel in the following conditions:
−
Duty Mode;
−
Fire condition;
−
Pre-Fire condition;
−
Fault condition;
−
Disabled component;
−
Information and adjustment.
To enter Access level 2, insert the key into the front panel in position
.
The following features of the fire control panel are accessible:
−
All features accessible at Level 1;
−
Suppression of the local sounder and switching off the outputs, activated upon fire
condition (see sections 8, 9 and 10);
−
Exit of Fire condition (see section 8);
−
System functions of the fire control panel without entering SetUp Mode (see section 13).
6.1.3. Access level 3
Accessible for personnel trained and authorized for:
−
Reconfiguration of specific data – of the protected site or of the fire control panel – saved
in the memory;
−
Maintenance of the fire control panel.
This level has two sublevels of access - 3A and 3B.
Level 3, sublevel 3A, is accessed through a password, entered at Access level 2. At this sublevel
the functions for reconfiguration of specific data for the protected site or the fire control panel are
accessible. (See section 14).
Level 3, sublevel 3B is accessed when the fire control panel is opened. The following features are
accessible:
−
Replacing a burnt fuse;
−
Adding, removing and replacing an additional module;
−
Connecting fire alarm lines and executive devices.
6.1.4. Access level 4
Accessible for trained and authorized by the Producer personnel to repair the fire control panel
and to modify the software. Special means are required to enter this level.
6.2. Indications and buttons for control
Table 1 gives detail desription of the indications for each status, Table 2 presents the basic
means for control. Appendix 1 shows the front panel of Fire control panel FS5100 with its visual
system for indication and control.