UniPOS
Fire Control Panel FS5100
Instruction Manual
Page 5
Revision 7/06.12
Of 47
1. Introduction
Fire Control Panel FS5100 is an up-to-date, high reliable, multifunctional and versatile unit,
providing the user with unexpected potential in the design, installation and operation of conventional
fire alarm systems.
Some of its main features and possibilities are:
−
Adjustment of operating modes and parameters of each fire alarm line via built in keypad;
−
User oriented menu dialogue for easy and convenient operation;
−
LCD for visualization of system checkup and setup modes;
−
LEDs indication for early warning of a break down or extreme conditions;
−
Ability to address automatic fire detectors and manual call points in groups;
−
Energy independent archive memory saving the event type, date and time, allowing for
detailed analysis of the actions of the authorized personnel and possible problems in the fire
protection process of the area;
−
User oriented test modes allowing for a total control of the site protected;
−
Built-in serial interface for connection to second level control devices, ability for connection via
telephone line and standard modem;
−
System expansion and functional modification (our goal is discontinuous improvement of the
fire alarm equipment features), no additional cabling necessary;
−
Compatible to random installation design, within the range of fire control panels resources.
All these are realizable via fire control panel’s keypad and after a detailed examination of the
instructions set herewith.
2. Terminology
ACCESS LEVEL – access level to various indications and control functions (see section 6.1).
ASSOCIATED OUTPUT –
controllable or relay output
, programmed by user to react (separately
in Fire condition I and Fire condition II) in Fire condition via selected
fire alarm line
.
CIRCUIT BOARD CONFLICT –
fatal fault condition
, due to detected conflict between current
configuration and configuration saved in the memory. Usually it occurs when an additional module
has been added, removed or replaced. In such case adjust the fire control panel.
CONTROLLABLE OUTPUT – potential output that monitors the serviceability of the connection
wires between the fire control panel and the executing device. Follow the special diagram for
connection. (Appendix 7 c).
DISABLED CONTROLLABLE OUTPUT –
the controllable output
is switched off (executing
devices can not be activated) and is not monitored for a fault condition. This feature is user defined.
The indication for a disabled controllable output is common light indication and text messages on the
LCD display.
DISABLED LINE – a switched off line, without power supply, not controlled for activated fire
detectors and fault condition. This condition is user defined. The indication for a disabled line is
common light indication and text messages on the LCD display.
FATAL FAULT CONDITION – fault condition that does not allow the fire control panel to continue
operation. The indication is common light indication, local sound indication and text messages on the
LCD display.
FIRE ALARM LINE (further on it will be referred as LINE) – automatic fire detectors and manual
call points, physically connected by the means of two-wire connection. The basic configuration of
FS5100 includes two lines; the maximum configuration includes eight lines. Up to 32 fire detectors
can be integrated into one line.