B-6
The AIF-100/CI provides the interface between the CCU-100 and the alarm
inputs in each of the AIF-100/AL and AIF-100/IO units connected to it. An AIF-
100/CI with its associated AIF-100/AL and AIF-100/IO units can be configured to
be equivalent to up to eight AIU-100 Alarm Interface Units. The AIF-100/CI has
a DIP switch that is used to determine the number of AIU-100 Alarm Interface
Units that the AIF-100/CI is equivalent to.
Each AIF-100/AL has 8 alarm inputs. Each AIF-100/IO has 4 alarm inputs.
Each AIF-100/CI supports up to a total of 32 AIF-100/AL and AIF-100/IO units.
Each AIF-100/AL and AIF-100/IO unit must have a unique address between 0-
31. The AIF-100/CI unit polls the AIF-100/AL units and AIF-100/IO units
connected to it for alarm inputs.
To program the alarm inputs on the AIF-100/AL and AIF-100/IO, the programmer
must know the number of AIU-100 units being replaced by the AIF-100/CI unit,
the address of the AIF-100/AL or AIF-100/IO, and the alarm input number on the
AIF-100/AL or AIF-100/IO.
EXAMPLE 1:
There is one AIF-100/CI, addressed as 0, connected to the CCU-100 Central
Control Unit. The AIF-100/CI has six AIF-100/AL units addressed 0-5 and two
AIF-100/IO units addressed as 6 and 7. Since each AIF-100/AL has 8 alarm
inputs and each AIF-100/IO has 4 alarm inputs, there are a total of 56 alarm
inputs.
Since 56 alarm inputs are greater than the number of alarm inputs (32) for one
AIU-100, but less than the number (64) for two AIU-100 units, this configuration
is equivalent to two AIU-100 units.
The alarm inputs on AIF-100/AL address 0 are AIU 0, 1 through 8. These will
appear on the JPD-100 display as alarms 1 through 8.
Содержание CCU-100HD
Страница 16: ......
Страница 23: ...1 7 ENVIRONMENTAL Temperature Limits 32 F to 122 F 0 C to 50 C Humidity Limits 0 to 95 non condensing...
Страница 24: ......
Страница 31: ...Figure 2 1 MODEL CCU 100 HD or CCU 100 HD X EQUIPMENT BLOCK DIAGRAM...
Страница 39: ...Figure 2 3 EQUIPMENT CONNECTIONS FOR CHANNELS 1 2 AND 3 NEAR CLOSE OPEN FAR...
Страница 41: ...Figure 2 4 EQUIPMENT CONNECTIONS FOR CHANNELS 4 AND 6...
Страница 43: ...Figure 2 5 1 EQUIPMENT CONNECTIONS FOR CHANNEL 5...
Страница 44: ...Figure 2 5 2 EQUIPMENT CONNECTIONS FOR CHANNEL 5...
Страница 45: ...Figure 2 5 3 EQUIPMENT CONNECTIONS FOR CHANNEL 5...
Страница 48: ......
Страница 49: ...2 25...
Страница 50: ...2 26...
Страница 68: ......
Страница 112: ......
Страница 124: ...A 10 SECTOR PROGRAMMING LOG cont Page 2 of 2 CAMERA NUMBER ______ SECTOR NAME COVERAGE 6 7 8 9 10 11 12 13 14 15...
Страница 126: ...A 12 PRESHOT PROGRAMMING LOG Page ___ of ___ CAMERA NUMBER _____ PreShot Name Coverage...
Страница 130: ...A 16 AIU 100 ALARM LOG Page ___ of ___ AIU ___ Alarm MultiCall Description of MultiCall...
Страница 132: ...A 18 MULTICALL LOG Page ___ of ___ MultiCall Assigned To Description...
Страница 146: ......