6.1.5
RECOMMENDED PROCEDURE FOR PROGRAMMING
The following steps should be carried out in the order given.
1.
System Design
Determine all system requirements; decide number of zones, zone LED Display
boards (if any); MAF module. Calculate the battery and PSU requirements as per
section 5.3. Decide on the battery capacity. Check that the physical size of the
battery fits in with the proposed mechanical arrangement. Fill out the configuration
forms provided in Appendix A with all of the programming details.
2.
E2 Init / Database re-initialise
With mains power off and the battery disconnected, fit any relay supervision links
required.
Fit links Lk7 and SW1 and turn mains power on to perform a database re-initialise as
per section 6.3.1. Set the time and date.
3.
Assign Access Codes
Enter programming mode using the default password. Assign access codes as per
section 6.4.2 Note that access code zero is the master code, and should be known
by the System Designer or Service Supervisor as appropriate.
4.
Assign RDU address and operating mode
The operating mode is set to AS4428.1 by default. If AS1603.4 operation is needed,
then the operating mode should be changed before any other programming. Refer to
section 6.4.1.
5.
Enter Text
Program text names for each item listed in section 6.4.3. There are several ways
that zone names can be created in the RDU. Refer to section 6.4.3.2.
6.
Enter Global Parameters
Assign values to all of the "global data" parameters that need to change from the
default settings. The menus and options which appear in the global data parameter
list are described in section 6.4.4.
7.
Enter System Configuration
Under the system config menu option, program the zone configuration, the number of
LED display boards and the mapping of zones to LEDs. These menus are described
in section 7.1.
8.
Checking
When all parameters have been programmed, exit program mode and either:
1.
Print the database (see section 6.3.5) and compare the printout against the
configuration forms (check each parameter for each item and tick off), or
2.
If a printer is not available, use "View Parameter" mode (see section 6.2.2)
and check each parameter against the configuration forms.
10.
Testing
Carefully test the RDU to verify that the programming is as required. This should
include generating an alarm for each point/zone for which the RDU displays alarms
to check that the RDU displays the alarm with the correct point/zone text.
11.
Save Database
When programming is complete and correct, save the database to a disk file if a
laptop/PC is available. See section 6.3.5.
Содержание RDU Mk2
Страница 58: ...RDU Mk2 Installation Programming Manual Document No LT0499 Programming Part 1 Page 6 4 8 April 2015 Issue 1 02...
Страница 59: ...Document No LT0499 RDU Mk2 Installation Programming Manual Programming Part 1 Issue 1 02 8 April 2015 Page 6 5...
Страница 61: ...Document No LT0499 RDU Mk2 Installation Programming Manual Programming Part 1 Issue 1 02 8 April 2015 Page 6 7...
Страница 105: ...Document No LT0499 RDU Mk2 Installation Programming Manual Programming Part 2 Issue 1 02 8 April 2015 Page 7 9...