Document No: LT0499
RDU Mk2 Installation & Programming Manual
Programming Part 2
Issue 1.02
8 April 2015
Page 7-33
SID:0 Start zone:32 End zone:35
Enter zones to delete then press DELETE
The zone range can be part of an existing range, as in this example:
SID 0
25
40 Existing zone range in database
SID 0
32
35
Entered zone range for deletion
SID 0
25
31
36
40 After deleting
Option 4 in the delete menu, allows deletion of the LED mapping for all zones.
1:Delete all zones
The delete options should be used carefully as the information cannot be recovered once
deleted.
7.8
TANDEM LCD MODE
Tandem LCD mode allows the LCD and keypad of an RDU to be "operated" from a
PC/terminal connected to the printer/programmer port. PanelX is a software program which
runs on a PC and uses Tandem LCD mode to interact with the RDU, allowing the RDU
keypad/LCD to be driven from the PC. PanelX presents an RDU-like keyboard on the
computer screen.
Refer to section 6.3.9 for information on connecting the RDU to a computer. With a plain
terminal or terminal emulator connected to the printer/programmer port of the RDU, tandem
mode can be initiated
by “pressing” the ENTER key and entering the Tandem LCD
password. A password of up to 12 characters can be programmed using option 7 from the
text programming menu.
NOTE :
When a terminal emulator is used to run tandem mode (instead of using PanelX),
the "C" (upper case C) key is used to exit tandem mode.
Tandem mode allows full programming of the RDU to be done including database load, save
and verify, and "remote text entry”. “Remote text entry” refers to the entering of text names
for zones and relays etc. on the programming terminal - refer to section 6.4.3.3. To initiate
remote text entry mode when tandem LCD mode is active (or PanelX is being used), enter
program mode and select the text programming option. The following text entry menu
should appear.
1:Site 2:Zone 3:Relay 4:Anc relay 5:Alarm text 6:Fault text 7:Tandem pwd
Remote text entry mode can then be initiated by pressing the EDIT key on the keypad. The
remote text entry prompt will appear as follows and text can then be entered.
Enter Znn, An, S, F, P, Q :
Содержание RDU Mk2
Страница 58: ...RDU Mk2 Installation Programming Manual Document No LT0499 Programming Part 1 Page 6 4 8 April 2015 Issue 1 02...
Страница 59: ...Document No LT0499 RDU Mk2 Installation Programming Manual Programming Part 1 Issue 1 02 8 April 2015 Page 6 5...
Страница 61: ...Document No LT0499 RDU Mk2 Installation Programming Manual Programming Part 1 Issue 1 02 8 April 2015 Page 6 7...
Страница 105: ...Document No LT0499 RDU Mk2 Installation Programming Manual Programming Part 2 Issue 1 02 8 April 2015 Page 7 9...