RDU Mk2 Installation & Programming Manual
Document No: LT0499
System Specifications
Page 3-10
8 April 2015
Issue 1.02
16 Zone Mimic Outputs are as follows:
J3-1:
Zone 6 Alarm
J3-2:
Zone 5 Alarm
J3-3:
Zone 7 Alarm
J3-4:
Zone 4 Alarm
J3-5:
Zone 8 Alarm
J3-6:
Zone 3 Alarm
J3-7:
0V
J3-8:
Zone 2 Alarm
J3-9:
0V
J3-10:
Zone 1 Alarm
J3-11:
0V
J3-12:
0V
J3-13:
0V
J3-14:
0V
J3-15:
+V EXT
J3-16:
+V EXT
J3-17:
+V EXT
J3-18:
+V EXT
J3-19:
Zone 9 Alarm
J3-20:
Zone 16 Alarm
J3-21:
Zone 10 Alarm
J3-22:
Zone 15 Alarm
J3-23:
Zone 11 Alarm
J3-24:
Zone 14 Alarm
J3-25:
Zone 12 Alarm
J3-26:
Zone 13 Alarm
16 Way Relay Module PA0470
Relay Output Rating :
1A @ 30VDC resistive
Relay Isolation
:
500Vdc
Option
:
Snip LK1 when supplying relay coil +24V externally.
This stops voltage being fed back into the Controller
through the display cables.
16 Way Relay Bd Outputs are as follows:
(a)
J1:RLY01
J1-1
RELAY 1-C
J1-2
RELAY 1-NC
J1-3
RELAY 1-NO
(b)
J2-J16:RLY02-RLY16 CONNECTOR
JX-1
RELAY X-C where X = relay number
JX-2
RELAY X-NC )
JX-3
RELAY X-NO )
Содержание RDU Mk2
Страница 58: ...RDU Mk2 Installation Programming Manual Document No LT0499 Programming Part 1 Page 6 4 8 April 2015 Issue 1 02...
Страница 59: ...Document No LT0499 RDU Mk2 Installation Programming Manual Programming Part 1 Issue 1 02 8 April 2015 Page 6 5...
Страница 61: ...Document No LT0499 RDU Mk2 Installation Programming Manual Programming Part 1 Issue 1 02 8 April 2015 Page 6 7...
Страница 105: ...Document No LT0499 RDU Mk2 Installation Programming Manual Programming Part 2 Issue 1 02 8 April 2015 Page 7 9...