Document No: LT0499
RDU Mk2 Installation & Programming Manual
Programming Part 1
Issue 1.02
8 April 2015
Page 6-25
2. Capture FIP time/date
If this option is enabled, then when a time/date update message is received from the
FIP, the RDU will update its own time and date.
6.4.4.3
Pass-On/Follow FIP Options
From the global data menu, the "Pass-on/follow FIP" option produces the following
sequence of menus.
1:Ancil 1 Isol >
1:WarnSys Isolate 2:WarnSys Operate >
1:ExtBell Isolate 2:ExtBell Operate >
If AS1603.4 mode of operation has been selected, then instead of the Warning System and
External Bell options above, the following menu appears
1:Bells Isol 2:Bells operate
If New Zealand mode of operation has been enabled then an additional menu appears as
follows
1:Services Restore 2:Trial Evac
The pass-on/follow menus allow a set of "Pass-on FIP/ Follow FIP/ Local control"
parameters to be programmed for each of the following. If the "pass-on" option is enabled,
then the RDU can send a command (e.g., isolate or de-isolate) to the FIP. If the "follow"
option is enabled then the RDU follows the state received from the FIP. If the "local control"
option is enabled then the command can be applied locally for that item. If "pass-on" is
enabled, then the corresponding "follow" option is enabled automatically and "local control"
is disabled.
1. Ancillary 1 isolate
2. Warning System isolate
3. Warning System operate
4. External Bell isolate
5. External Bell operate
6. Bells isolate
7. Bells operate
8. Trial Evac (New Zealand mode only)
9. Services restore (New Zealand mode only)
The Warning System and External Bell options appear only in AS4428.1 mode and the Bells
isolate and Bells operate options appear only in AS1603.4 mode.
For each of the above items, there are three options that can be enabled or disabled as
follows. Some options are not applicable to some items.
1. Pass-on FIP
2. Follow FIP
3. Local control
Содержание RDU Mk2
Страница 58: ...RDU Mk2 Installation Programming Manual Document No LT0499 Programming Part 1 Page 6 4 8 April 2015 Issue 1 02...
Страница 59: ...Document No LT0499 RDU Mk2 Installation Programming Manual Programming Part 1 Issue 1 02 8 April 2015 Page 6 5...
Страница 61: ...Document No LT0499 RDU Mk2 Installation Programming Manual Programming Part 1 Issue 1 02 8 April 2015 Page 6 7...
Страница 105: ...Document No LT0499 RDU Mk2 Installation Programming Manual Programming Part 2 Issue 1 02 8 April 2015 Page 7 9...