RDU Mk2 Installation & Programming Manual
Document No: LT0499
Programming Part 2
Page 7-4
8 April 2015
Issue 1.02
9. Hide
If enabled, the zone does not appear in zone recalls unless the MapMAF or Total options
are enabled for the zone. I.e., mapMAF and Totals options override the "hide" option.
10. Log
If enabled, events for the zone are logged to the printer and history. If disabled, no
events are logged for the zone(s).
11. Total
For MAF mapped zones, this setting is ignored. MAF mapped zones always map to
totals, common LEDs and logic tokens (e.g. NMA, NMF). For non-MAF zones, if the
"Total" option is set false, then the zone is not included in totals, common LEDs etc.
12. Alarm test
If enabled, an alarm test may be initiated on the zone at the RDU.
13. Fault test
If enabled, a fault test may be initiated on the zone at the RDU.
14. Output zone
If enabled, the zone is treated as a relay/ ACZ type zone rather than an alarm zone.
This means that off normal conditions on the zone are treated as "activated" rather than
"alarm". The status bits sent from the FIP to the RDU for a zone include alarm/activate,
fault and isolate. The "Output zone" setting is needed at the RDU to determine whether
the alarm/activate state is alarm or activate.
15. MapMAF
If enabled, the zone maps to the MAF. If the RDU has a MAF board fitted, then the MAF
relays (alarm, fault and isolate) are driven from MAF mapped zones. A number of logic
tokens distinguish between MAF mapped zones and non-MAF mapped zones.
16. MapANC1
If enabled, the zone maps to the ancillary 1 relay. This means that ancillary relay 1 will
be energised for a non-isolated alarm on the zone.
17. MapExtBell
If enabled, the zone maps to the External Bell. This means that External Bell outputs at
the RDU will be energised for a non-isolated alarm on the zone. This option is available
only in AS4428.1 mode.
18. MapWarnSys
If enabled, the zone maps to the Warning System. This means that Warning System
outputs at the RDU will be energised for a non-isolated alarm on the zone. This option
appears only in AS4428.1 mode.
19. MapANC2
If enabled, the zone maps to the ancillary 2 relay. This means that ancillary relay 2 will
be energised for a non-isolated alarm on the zone. This option appears only in
AS1603.4 mode.
20. MapBells
If enabled, the zone maps to the Bells. This means that the Bells outputs at the RDU will
be energised for a non-isolated alarm on the zone. This option appears only in
AS1603.4 mode.
Содержание RDU Mk2
Страница 58: ...RDU Mk2 Installation Programming Manual Document No LT0499 Programming Part 1 Page 6 4 8 April 2015 Issue 1 02...
Страница 59: ...Document No LT0499 RDU Mk2 Installation Programming Manual Programming Part 1 Issue 1 02 8 April 2015 Page 6 5...
Страница 61: ...Document No LT0499 RDU Mk2 Installation Programming Manual Programming Part 1 Issue 1 02 8 April 2015 Page 6 7...
Страница 105: ...Document No LT0499 RDU Mk2 Installation Programming Manual Programming Part 2 Issue 1 02 8 April 2015 Page 7 9...