Document No: LT0499
RDU Mk2 Installation & Programming Manual
Programming Part 1
Issue 1.02
8 April 2015
Page 6-9
6.2
PROGRAMMING OR VIEWING THE DATABASE
6.2.1
GENERAL
To program or view the database, from the base display, press the "SET" key and the
following menu appears.
1 Set Time 2 Set Date 3 View database 4 Program database >
The arrow (>) at the right hand end indicates that a second menu can be accessed using the
right arrow key. Options 1, 2 in the above menu are operator accessible and do not require
a password.
Options 3:View database and 4:Program database, require an access code to be entered.
View database operation is described in the Section 6.2.2. A description of program mode
operation begins in Section 6.4. Fig 6.1.2 shows the structure of the menus available in
program mode.
Pressing the right arrow key from the above menu produces a second menu as follows.
1:Verify database 2:PSU fault inhibit
Option 1: Verify database allows the database to be compared to one held on the disk of a
PC/laptop. Refer to Section 6.3.6.
Option 2: PSU fault inhibit is an operator function described in the Operator's manual
LT0494 (AS1603.4) and LT0495 (AS4428.1).
6.2.2
VIEW DATABASE
To view the configuration database without changing it, from the base display, press the SET
key and select option 3 View database. A password must then be entered. When in view
database mode, the same menus used in program mode to modify the database, are used
to view the database. The database write protect link LK7 should be left in the "protect"
position when viewing the database. Processing of alarms continues while in view database
mode.
6.3
DATABASE OPERATIONS, INITIALISING,
ACCESSING, SAVING
6.3.1
INITIALISING THE DATABASE
The database can be reinitialised by powering up with the E2INIT link fitted as described
below. A default database is assigned and all previous programmed data is lost.
Steps
1. Fit the Mini-jump on the database write protect link, (Lk7 - top right of controller board) in
the PROTECT position, (i.e., not write enabled).
2. With the batteries disconnected, turn the FIP mains power off.
3. Fit a mini-jump (i.e., short the two pins) to the E2INIT link (SW1 - top centre of
controller), then turn the power on.
Содержание RDU Mk2
Страница 58: ...RDU Mk2 Installation Programming Manual Document No LT0499 Programming Part 1 Page 6 4 8 April 2015 Issue 1 02...
Страница 59: ...Document No LT0499 RDU Mk2 Installation Programming Manual Programming Part 1 Issue 1 02 8 April 2015 Page 6 5...
Страница 61: ...Document No LT0499 RDU Mk2 Installation Programming Manual Programming Part 1 Issue 1 02 8 April 2015 Page 6 7...
Страница 105: ...Document No LT0499 RDU Mk2 Installation Programming Manual Programming Part 2 Issue 1 02 8 April 2015 Page 7 9...