72
10
TROUBLESHOOTING
10.1
Preliminary Check
Before performing any troubleshooting operation and before removing
the autoclave’s cover, check the following:
1. Electrical power:
Verify that:
a.
Power
supply
is
1ph/208 VAC
for
model
2540
and
3ph/208 VAC
for
model
3870.
b. It has an earth wire.
2. Mineral free water: ½” connection. Water pressure, after the
pressure reducer (as indicated on the pressure
reducer’s gauge) must be 7-30 psi.
3. City water:
½” connection. Water pressure, after the
pressure reducer (as indicated on the pressure
reducer’s gauge) must be 15-58 psi.
4. Drain:
The drain tube must be connected directly to
the sewage. It must be straight and not
elevated to any degree. The drain opening
should be within 1 foot of the rear of the unit
and no higher than 16” above the floor.
In order to locate any malfunctioning component perform the “in-out
test” this test enables the technician to activate most of the components
and test the analog and digital inputs, This enables the technician to
verify whether the problem is caused by an end item, by the control
system or by any other reason.
Before any operation or test on the autoclave perform a visual check
for loose parts or for signs of over-heating and burnt components.
10.1.1
Manual Valves
There are four (4) manual control valves (see piping diagram)
and the technician must verify that they are open as instructed
below.
There is one manual control valve on the incoming mineral
free water line.
There are two valves on the feed water line and there is one
valve that acts as a bypass to the steam trap.
The three incoming waterline valves are used to regulate flow
and should be opened 2 –3 full turns. One controls feed water
flow to the vacuum pump reservoir, one controls flow to the
mineral free water reservoir and one controls flow of feed
water for cooling the exhaust drain. (Since the majority of
drains are made of PVC pipe the exhaust temp needs to
remain below 140ºF. the cooling water valve is used to
maintain drain temperatures well below 140ºF.
The
steam
trap
bypass
valve
is
used to control steam escaping
from the chamber and should be open ¼ - ½ turn. Restricting
the flow of steam too much or too little will result in a system
failure.
To
set
or
check
the
valves,
close them fully make an indicator
mark if one is not present and open the proper number of
turns.
Содержание 2540 EHS
Страница 10: ...9 REAR VIEW...
Страница 17: ...16 Layout diagram of the ANL T2 is provided below ANL T2 BOARD Top View Bottom View...
Страница 19: ...18 AC T1 BOARD Top View Bottom View...
Страница 30: ...29 6 4 Input Output Graph...
Страница 31: ...30...
Страница 32: ...31...
Страница 33: ...32...
Страница 34: ...33...
Страница 35: ...34...
Страница 66: ...65...
Страница 68: ...67...
Страница 120: ...119 VESSEL ASSEMBLY Model 2540 EHS Model 3870 EHS...
Страница 121: ...120 OUTER CABINET ASSEMBLY Model 2540 EHS Model 3870 EHS...
Страница 122: ...121 TRAY HOLDER For model 2540 TRH254 0009 For model 3870 TRH387 0001...
Страница 123: ...122 TRAY TRAY HANDLE CMT240 0001 MODEL SIZE CAT No 2540 TRY240 0001 Big TRY387 0001 3870 Small TRY387 0003...
Страница 126: ...125 PIPING DRAWING FOR 2540 EHS...
Страница 127: ...126 PIPING DRAWING FOR 3870 EHS...
Страница 128: ...127 ELECTRICAL DRAWING FOR 2540 EHS...
Страница 129: ...128 ELECTRICAL DRAWING FOR 3870 EHS TILL S N 2307039...
Страница 130: ...129 ELECTRICAL DRAWING FOR 3870 EHS AFTER S N 2307040...