3-2-6.Setting and readout of preset timer
Type of command
STPRdddd・・・・
To set preset value dddd・・・・・ in decimal to timer.
Unit is ms.
Maximum timer set value is 1,099,511,627 ms.
STPRFdddd・・・・
To set preset value dddd・・・・・ in decimal to timer.
Unit is μs.
Maximum timer set value is 1,099,511,627,775 μs.
Inquiry command format
TPR?
To read out preset timer value.
Reply
00123456
Reply data is 8 digit decimal value.
4294967000
(If reply data is over 8 digit, the digit is as the timer digit.)
Unit is ms.
TPRF?
To read out preset count value.
Reply
00123456
Reply data is 8 digit decimal value.
4294967000
(If reply data is over 8 digit, the digit is as the timer digit.)
Unit is μs.
Type of command
STRT
Enable counter start.
Type of command
STOP
Enable counter stop.
Type of command
RDAL?
To read all counter channels and timer
Reply
1234567890 2345678901 3456789012 ・・・・・ 0123456789
These data are 10 digit number in decimal.
The data order is CH0 CH1 CH2 ・・・・・・ CH7 timer.
If reply data is over 10 digit, the digit is as the value digit.
Unit is cts for counter and μs for timer.
Type of command
CLAL?
To clear all counter channels and timer
3-3.Commands of counter operation
3-3-1.Counter start
3-3-2.Counter stop
3-4.Read-out and clear commands for counter and timer
3-4-1.Read-out and clear commands for all counter and timer
10/15