10-13.Set up safe mode value
Command
ID 46 29 DD 00 (CRC)
Syntax
Description
ID
Address of setting module 1~247
46
Function Code
29
Set up safe mode value
DD
DD: Safe mode digital output value
00
Reserved code
Response
ID 46 29 00(CRC)
ID 46 29 00 ……Command valid.
ID C6 00 (CRC)
ID C6 (CRC) C6:Function Code 00: Reserved code
Example:
Send Command:”01 46 29 14 00”…….Set up TRP-C29U’s safe mode value.
Response:”01 46 29 00”.
Then send “01 46 0B 12 00”……Waiting the watchdog timeout until the digital output value
become “14”.
Error Response: “01 C6 00”……Error code.
*Safe mode: Digital output states when watchdog timeout.
10-14.Read safe mode value
Command
ID 46 2A 00 (CRC)
Syntax
Description
ID
Address of setting module 1~247
46
Function Code
2A
Read power on mode
00
Reserved code
Response
ID 46 2A DD (CRC)
00 46 2A 00 ……Module command line
DD
: Safe mode value
ID C6 00 (CRC)
ID C6 (CRC) C6:Function Code 00: Reserved code
Example:
43