Command
ID 46 07 00 (CRC)
Syntax
Description
ID
Address of setting module 1~247
46
Function Code
07
Read module’s Firmware
00
Reserved code
Response
ID 46 07
YY
MM
DD
00(CRC)
ID 46 07 ……Module command Line
YY
:Year
MM
:Month
DD:
Date
00 : Reserved code
ID C6 00 (CRC)
ID C6 (CRC) C6:Function Code 00: Reserved code
Example:
Send Command:”01 46 07 00”…….Set up TRP-C29U’s configuration.
Response:”01 46 07 09 07 03 00“…JUY. 03.2009 TRP-C29U Firmware Version.
Error Response: “01 C6 00”……Error code.
10-6.Read module reset status
Command
ID 46 08 00(CRC)
Syntax
Description
ID
Address of setting module 1~247
46
Function Code
08
Read Module Reset status
00
Reserved code
Response
ID 46 08 0D 00 (CRC)
D=0 Have been read, D=1 Have been reset
ID C6 00 (CRC)
ID C6 (CRC) C6:Function Code 00: Reserved code
Example:
Send Command:”01 46 08 00”…Read the module’s digital input status.
Response:”01 46 08 1 00 ..have been reset.
10-7.Reset