Send Command:”01 46 2A 00”…….Read TRP-C24’s safe mode value.
Response:”01 46 2A 12 “…Safe mode value is “12 ”.
Error Response: “01 C6 00”……Error code.
10-15. System stand by (Host OK!)
Command
ID 46 2F 00 (CRC)
Syntax
Description
ID
Address of setting module 1~247
46
Function Code
2F
System stand by
00
Reserved code
Response
No Response
10-16.Set up single channel and latch status
Command
ID 05 SS NN DD 00 (CRC)
Syntax
Description
ID
Address of setting module 1~247
05
Function Code
SS
SS = 00 Set up single channel output
SS= 01 ->Clear latch status (NN=0, DD=0)
SS= 02 ->Clear single channel counter value(DD=00)
NN
NN=00~07=DO0~DO7
DD
Digital output value DD=00 disable, DD=FF enable
00
Reserved code
Response
ID 05 SS NN DD 00 (CRC)
Command valid
ID 85 FF (CRC)
Watchdog mode status