Command
ID 46 09 00 (CRC)
Syntax
Description
ID
Address of setting module 1~247
46
Function Code
09
Module Reset
00
Reserved code
Response
ID 46 09 00 (CRC)
Command valid
ID C6 00 (CRC)
ID C6 (CRC) C6:Function Code 00: Reserved code
Example:
Send Command:”01 46 09 00”…Read the module’s digital input status.
Response:”01 46 09 00 ..Command valid.
Error Response: “01 C6 00”…Error code.
10-8.Set up watchdog timeout value or disable watchdog
Command
ID 46 0B WS 00 (CRC)
Syntax
Description
ID
Address of setting module 1~247
46
Function Code
0B
Set up watchdog function
WS
WS=00 Watchdog Disable
Watchdog timer from 01~FF (100ms~25.5 Sec)
00
Reserved code
Response
ID 46 0B 00(CRC)
00 ID 46 0B 00 ……Command valid
ID C6 00 (CRC)
ID C6 (CRC) C6:Function Code 00: Reserved code
Example:
Send Command:”01 46 0B 05 00”…….Set up TRP-C29U’s watchdog timer=500ms.
Response:”01 46 0B 00“…
Command valid
.
Error Response: “01 C6 00”……Error code.
10-9.Read watchdog status