Command
$ID2(CHK)(cr)
Syntax
Description
$
First leading code
ID
Address of setting module 00~FF(HEX)
2
Read configuration
CHK
Checksum
(cr)
Carriage return
Response
!IDPPBBDD(CHK)(cr) Command valid
PP: Digital I/O type=40
BB: Baud rate
DD=Data format (See data format table)
Module model BIT0~2=“000”:TRP-C28
“
001” TRP-C24
“
010” TRP-C26
“
011” TRP-C29U
?ID(CHK)(cr)
Command Invalid
Example:
Send command:$012…Read configuration .
Response:”! 01400603”……. DIO type=40,Baud-Rate=9600 (See 7.2) ,Data format=03 Input
counter :rising ,Checksum= disable, Model=3….TRP-C29UM.
8-13.Reset
Command
$IDRS(CHK)(cr)
Syntax
Description
$
First leading code
ID
Address of setting module 00~FF(HEX)
RS
Reset the TRP-C29U module
CHK
Checksum
(cr)
Carriage return
Response
!ID(CHK)(cr)
Command valid
?ID(CHK)(cr)
Command Invalid
Example:
Send command:”$01RS”…….Reset TRP-C29UM.
Response:”!01 ”……… …………..Have been reset.