Digital control panel
Fig. 2: Dimensions
Note: The overall dimensions depend on the frame that
has been selected for the switch.
Fig. 3
1
Service push button
2
Service LED
Notes on installation
The control panel is suitable for installation on a junction
box. You can connect the bus cable to the control panel
with a screw terminal. For pre-wiring you can remove
the screw terminal from the panel.
We recommend using deep junction boxes as they pro-
vide more space for cables.
Attach the LON interface card to the screws (by others)
in the junction box; max. torque for the screws is
0.8 Nm. Place the mounting ring of the LON interface
card flat on the face of the wall; do not cover it with paint
or wallpaper.
Technical data
Supply voltage
15...24 V= (±10%) or
24 V~ (±10%)
Power consumption
1.3 W / 1.5 VA
Interface
FTT, free topology
Measuring range
0...+50 °C
Accuracy (21 °C)
±0.5 K
Response time
Time constant t
63
15
minutes
Screw terminals
1.5 mm² max.
Protection level
IP 30 to EN 60529
Ambient temperature
0...50 °C
Transport
-10...50 °C / max. 85% rh,
no condensation
Making electrical connections
Wiring > Stand-alone operation
Single room control system FSL
‑
CONTROL II
9
Содержание FSL-CONTROL II
Страница 64: ...Configuring interfaces to the central BMS BACnet MS TP interface Single room control system FSL CONTROL II 64...
Страница 74: ...Configuring interfaces to the central BMS Modbus RTU interface Single room control system FSL CONTROL II 74...
Страница 75: ...Configuring interfaces to the central BMS Modbus RTU interface Single room control system FSL CONTROL II 75...
Страница 77: ...Single room control system FSL CONTROL II 77...
Страница 78: ...Single room control system FSL CONTROL II 78...
Страница 79: ...Single room control system FSL CONTROL II 79...