He, 21 March 2017
C:\Users\SCHMITHUESEN\Desktop\170321_Datenpunkte XAC_EN.docx
6
nviFanSpeed
SNVT_switch
Function: Default setting of fan stage (fan speed)
LON
BACnet
Modbus
Description
state
value
(Register 15)
1
0
1
1
Fan stage
OFF
1
20
2
10241
Fan stage 1
1
40
3
20481
Fan stage 2
1
60
4
30721
Fan stage 3
1
80
5
40961
Fan stage 4
1
100
6
51201
Fan stage 5
0
XXX
7
0
Automatic
mode
Modbus: e.g. 20*2 = 40 => 28Hex + State 01 => 2801 Hex => 10241
Configuring interfaces to the central BMS
List of data points
Single room control system FSL
‑
CONTROL II
46