He, 21 March 2017
C:\Users\SCHMITHUESEN\Desktop\170321_Datenpunkte XAC_EN.docx
2
nviApplicMode
SNVT_hvac_mode
Function: Operating mode default setting
LON Identifier
BACnet
Modbus
(Register 0)
Description
HVAC_NUL
1
255
Invalid = inactive
HVAC_NIGHT_PURGE
6
4
Night purge
activation
nviMode
SNVT_occupancy
Function: Operating mode default setting by central BMS
LON value
Identifier
BACnet
value
Modbus
value
(Register 1)
Description
0
OC_OCCUPIED
1
0
Occupied
1
OC_UNOCCUPIED
2
1
Unoccupied
2
OC_BYPASS
3
2
Boost
3
OC_STANDBY
4
3
Standby
255
OC_NUL
5
255
invalid
nviOccSensor
SNVT_occupancy
Function: Operating mode default setting by a PIR sensor (by others)
LON value
Identifier
BACnet
value
Modbus
value
(Register 2)
Description
0
OC_
OCCUPIED
1
0
Occupied
1
OC_
UNOCCUPIED
2
1
Unoccupied
2
OC_ BYPASS
3
2
Boost
3
OC_STANDBY
4
3
Standby
255
OC_ NUL
5
255
invalid
Configuring interfaces to the central BMS
List of data points
Single room control system FSL
‑
CONTROL II
42
Содержание FSL-CONTROL II
Страница 64: ...Configuring interfaces to the central BMS BACnet MS TP interface Single room control system FSL CONTROL II 64...
Страница 74: ...Configuring interfaces to the central BMS Modbus RTU interface Single room control system FSL CONTROL II 74...
Страница 75: ...Configuring interfaces to the central BMS Modbus RTU interface Single room control system FSL CONTROL II 75...
Страница 77: ...Single room control system FSL CONTROL II 77...
Страница 78: ...Single room control system FSL CONTROL II 78...
Страница 79: ...Single room control system FSL CONTROL II 79...