He, 21 March 2017
C:\Users\SCHMITHUESEN\Desktop\170321_Datenpunkte XAC_EN.docx
9
nvoSupplyAirTemp
SNVT_temp_p
Function: Output of the supply air actual temperature to the central BMS
LON value
BACnet value
Modbus value
(Register 16)
Enter with 2 decimal
places, e.g. 23 °C
23.00
Enter with 2 decimal
places, e.g. 23 °C
23.00
Enter without decimal
places, multiply with 100,
e.g. 23.00 °C
2300
Invalid: 327,67
Invalid: 327,67
Invalid: 327,67
nvoMode / ActMode
SNVT_occupancy
Function: Output of the actual operating mode to the central BMS
LON value
Identifier
BACnet
value
Modbus
value
(Register 17)
Description
0
OC_OCCUPIED
1
0
Occupied
1
OC_UNOCCUPIED
2
1
Unoccupied
2
OC_BYPASS
3
2
Boost
3
OC_STANDBY
4
3
Standby
255
OC_NUL
5
255
invalid
nvoExtraTime / ActExtraTime
SNVT_switch
Feedback to the central BMS whether operating time extension has been enabled
LON
BACnet
Modbus
Description
state
value
(Register 18)
0
XXX
0
0
1 = operating
time extension
has been
enabled
1
XXX
1
1
Configuring interfaces to the central BMS
List of data points
Single room control system FSL
‑
CONTROL II
49
Содержание FSL-CONTROL II
Страница 64: ...Configuring interfaces to the central BMS BACnet MS TP interface Single room control system FSL CONTROL II 64...
Страница 74: ...Configuring interfaces to the central BMS Modbus RTU interface Single room control system FSL CONTROL II 74...
Страница 75: ...Configuring interfaces to the central BMS Modbus RTU interface Single room control system FSL CONTROL II 75...
Страница 77: ...Single room control system FSL CONTROL II 77...
Страница 78: ...Single room control system FSL CONTROL II 78...
Страница 79: ...Single room control system FSL CONTROL II 79...