Configuring interfaces to the central BMS
Modbus RTU interface
Single room control system FSL
‑
CONTROL II
73
9
Register
address
Useful data
name
Direction
EM / GG
Modbus
values
Modbus
default
SPI bytes
Encoding / Unit / Resolution
30
Alarm2
GG -> EM
0 - 1
0
Low, (High=0)
31
Release
GG -> EM
0 - 1
0
Low, (High=0)
32
Status
GG -> EM
uint16
0
High, Low
33
RTemp
GG -> EM
sint16
0x7FFF
High, Low
Unit 0.01°C
34
Sum_Sup
GG -> EM
uint16
0
High, Low
Unit l/s
35
Sum_Exh
GG -> EM
uint16
0
High, Low
Unit l/s
36
SystemDevices
GG -> EM
uint16
0
High, Low
no unit
37
ActFire
GG -> EM
0 - 1
0
Low, (High=0)
38
FanForce
EM -> GG
0 - 1
0
Low, (High=0)
39
ActFanForce
GG -> EM
0 – 1
0
Low, (High=0)
Bit list for X-AIRCONTROL
The Read Coils and Write Single Coil functions are used to access binary data;
this is in addition to the above register accesses.
The Write Single Coil function encodes the binary value by (false -> 0x0000,
true -> 0x0001) and writes the result to the register.
For bit addresses 0-15 the Read Coils function reads the registers and re-
encodes to bit values by using bit 0 of the register values.
Bit addresses 16-22 are copies of the Status register (address 32).
Direction column:
EM -> GG Reading and writing of bits
GG -> EM Reading of bits
------------------------------------------------
Bit Useful data Direction
address register name EM / GG
------------------------------------------------
Bits from several registers
0 StartPCM EM -> GG
1 Fire EM -> GG
2 Window EM -> GG
3 ExtraTime EM -> GG
4 FanForce EM -> GG
------------------------------------------------
8 ActFanForce GG -> EM
9 ActFire GG -> EM
10 ActWindow GG -> EM
11 ActExtraTime GG -> EM
12 Falarm GG -> EM
13 Alarm1 GG -> EM
14 Alarm2 GG -> EM
15 Release GG -> EM
------------------------------------------------
Bits from Status register
16 Powersupply GG -> EM
17 EMFSLIO GG -> EM
18 FanBlocked GG -> EM
19 SensorError GG -> EM
20 FilterAlarm GG -> EM
21 FlowControl GG -> EM
22 DamperCalibration GG -> EM
------------------------------------------------
Содержание FSL-CONTROL II
Страница 64: ...Configuring interfaces to the central BMS BACnet MS TP interface Single room control system FSL CONTROL II 64...
Страница 74: ...Configuring interfaces to the central BMS Modbus RTU interface Single room control system FSL CONTROL II 74...
Страница 75: ...Configuring interfaces to the central BMS Modbus RTU interface Single room control system FSL CONTROL II 75...
Страница 77: ...Single room control system FSL CONTROL II 77...