Configuring interfaces to the central BMS
BACnet MS/TP interface
Single room control system FSL
‑
CONTROL II
62
PICS_X-AIRCONTROL_v1.0.doc
- 6 -
Multistate Value Objects
Property
Remark / Value
RW
Object_Identifier
multistate-value, instance 1 … 9
R
Object_Name
R
Object_Type
MULTISTATE_VALUE (19)
R
Present_Value
State
Status_Flags
IN_ALARM:
0
FAULT:
0
OVERRIDDEN:
0
OUT_OF_SERVICE: 0
R
Event_State
NORMAL (0)
R
Out_Of_Service
FALSE (0)
R
Number_Of_States
R
State_Text
R
R: Read Property, W: Write Property, -E: Storage in EEPROM
Instance Number_
Of_States
Object_Name
State
State_Text
Present_Value
1
3
“COV-Mode”
1
2
3 (initial)
“Disabled”
“Local Broadcast”
“Global Broadcast”
RW-E
2
15
“ApplicMode”
1 (initial)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
“HVAC_NUL”
“HVAC_AUTO”
“HVAC_HEAT”
“HVAC_MRNG_WRMUP”
“HVAC_COOL”
“HVAC_NIGHT_PURGE”
“HVAC_PRE_COOL”
“HVAC_OFF”
“HVAC_TEST”
“HVAC_EMERG_HEAT”
“HVAC_FAN_ONLY”
“HVAC_FREE_COOL”
“HVAC_MAXHEAT”
“HVAC_ECONOMY”
“HVAC_DEHUMID”
RW
3
15
“ActApplicMode”
1 (initial)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
“HVAC_NUL”
“HVAC_AUTO”
“HVAC_HEAT”
“HVAC_MRNG_WRMUP”
“HVAC_COOL”
“HVAC_NIGHT_PURGE”
“HVAC_PRE_COOL”
“HVAC_OFF”
“HVAC_TEST”
“HVAC_EMERG_HEAT”
“HVAC_FAN_ONLY”
“HVAC_FREE_COOL”
“HVAC_MAXHEAT”
“HVAC_ECONOMY”
“HVAC_DEHUMID”
R
Содержание FSL-CONTROL II
Страница 64: ...Configuring interfaces to the central BMS BACnet MS TP interface Single room control system FSL CONTROL II 64...
Страница 74: ...Configuring interfaces to the central BMS Modbus RTU interface Single room control system FSL CONTROL II 74...
Страница 75: ...Configuring interfaces to the central BMS Modbus RTU interface Single room control system FSL CONTROL II 75...
Страница 77: ...Single room control system FSL CONTROL II 77...
Страница 78: ...Single room control system FSL CONTROL II 78...
Страница 79: ...Single room control system FSL CONTROL II 79...