Configuring interfaces to the central BMS
Modbus RTU interface
Single room control system FSL
‑
CONTROL II
72
8
Register
address
Useful data
name
Direction
EM / GG
Modbus
values
Modbus
default
SPI bytes
Encoding / Unit / Resolution
7
RelHumid
EM -> GG
0 - 100
0
Low, (High=0)
Unit %
8
StartPCM
EM -> GG
0 - 1
0
Low, (High=0)
9
VOC_Room
EM -> GG
uint16
0
High, Low
Unit ppm
10
VOC_Outside
EM -> GG
uint16
0
High, Low
Unit ppm
11
Fire
EM -> GG
0 - 1
0
Low, (High=0)
12
Window
EM -> GG
0 - 1
0
Low, (High=0)
13
ExtraTime
EM -> GG
0 - 1
0
Low, (High=0)
14
ChangeOver
EM -> GG
0 - 2
0
Low, (High=0)
0 = off
1 = cooling
2 = heating
15
FanSpeed
EM -> GG
see Encoding
0; 0
High, Low
High-Byte: Value,
Low-Byte: 0 Auto, 1 Hand
0x0001 = 0; 1 = Off
0x2801 = 40; 1 = Level 1
0x5001 = 80; 1 = Level 2
0x7801 = 120; 1 = Level 3
0xA001 = 160; 1 = Level 4
0xC801 = 200; 1 = Level 5
0x0000 = 0; 0 = Auto
16
DischAirTemp
GG -> EM
sint16
0x7FFF
High, Low
Unit 0.01°C
17
ActMode
GG -> EM
255,
0, 1, 2, 3
255
Low, (High=0)
255 = Nul
0 = Occupied
1 = Unoccupied
2 = Boost
3 = Standby
18
ActExtraTime
GG -> EM
0 - 1
0
Low, (High=0)
19
EffectSetpt
GG -> EM
sint16
0x7FFF
High, Low
Unit 0.01°C
20
ActWindow
GG -> EM
0 - 1
0
Low, (High=0)
21
ActFanSpeed
GG -> EM
see Encoding
0; 0
High, Low
High-Byte: Value,
Low-Byte: 0 Auto, 1 Hand
0x0001 = 0; 1 = Off, Hand
0x2801 = 40; 1 = Level 1
0x5001 = 80; 1 = Level 2
0x7801 = 120; 1 = Level 3
0xA001 = 160; 1 = Level 4
0xC801 = 200; 1 = Level 5
0x0000 = 0; 0 = Off, Auto
0x2800 = 40; 0 = Level 1
0x5000 = 80; 0 = Level 2
0x7800 = 120; 0 = Level 3
0xA000 = 160; 0 = Level 4
0xC800 = 200; 0 = Level 5
22
ActApplicMode
GG -> EM
255,
0 – 10,
12 – 14
255
Low, (High=0)
255 = HVAC_NUL
0 = HVAC_AUTO
1 = HVAC_HEAT
2 = HVAC_MRNG_WRMUP
3 = HVAC_COOL
4 = HVAC_NIGHT_PURGE
5 = HVAC_PRE_COOL
6 = HVAC_OFF
7 = HVAC_TEST
8 = HVAC_EMERG_HEAT
9 = HVAC_FAN_ONLY
10 = HVAC_FREE_COOL
12 = HVAC_MAXHEAT
13 = HVAC_ECONOMY
14 = HVAC_DEHUMID
23
ActOutsideTemp
GG -> EM
sint16
0x7FFF
High, Low
Unit 0.01°C
24
SetptOffset
GG -> EM
sint16
0x7FFF
High, Low
Unit 0.01°C
25
ActRoomTemp
GG -> EM
sint16
0x7FFF
High, Low
Unit 0.01°C
26
ActRelHumid
GG -> EM
0 - 100
0
Low, (High=0)
Unit %
27
ActVOC_Room
GG -> EM
uint16
0
High, Low
Unit ppm
28
FAlarm
GG -> EM
0 - 1
0
Low, (High=0)
29
Alarm1
GG -> EM
0 - 1
0
Low, (High=0)
Содержание FSL-CONTROL II
Страница 64: ...Configuring interfaces to the central BMS BACnet MS TP interface Single room control system FSL CONTROL II 64...
Страница 74: ...Configuring interfaces to the central BMS Modbus RTU interface Single room control system FSL CONTROL II 74...
Страница 75: ...Configuring interfaces to the central BMS Modbus RTU interface Single room control system FSL CONTROL II 75...
Страница 77: ...Single room control system FSL CONTROL II 77...
Страница 78: ...Single room control system FSL CONTROL II 78...
Страница 79: ...Single room control system FSL CONTROL II 79...