He, 21 March 2017
C:\Users\SCHMITHUESEN\Desktop\170321_Datenpunkte XAC_EN.docx
10
nvoEffectSetPt
SNVT_temp_p
Function: Feedback of the effective room temperature setpoint value to the central
BMS
LON value
BACnet value
Modbus value
(Register 19)
Enter with 2 decimal
places, e.g. 26 °C
26.00
Enter with 2 decimal
places, e.g. 26 °C
26.00
Enter without decimal
places, multiply with 100,
e.g. 26.00 °C
2600
Invalid: 327,67
Invalid: 327,67
Invalid: 327,67
nvoWindow / ActWindow
SNVT_switch
Function: Feedback whether a window contact has been enabled
LON
BACnet
Modbus
Description
state
value
(Register 20)
0
XXX
0
0
Window
contact
disabled
1
XXX
1
1
Window
contact
enabled
Configuring interfaces to the central BMS
List of data points
Single room control system FSL
‑
CONTROL II
50