LED-Driver
LCO EXC3/ADV3 OTD
Product Manual
Страница 1: ...LED Driver LCO EXC3 ADV3 OTD Product Manual ...
Страница 2: ...patibility between LED module and LED Driver 13 4 1 Comparison of data sheet values with a 5 point guideline 13 4 2 Practical tests 15 4 3 Application of the 5 point guideline 16 5 Installation notes 22 5 1 Safety information 22 5 2 Function of the earth terminal 23 5 3 Routing the wires 25 5 4 External fuse for DC operation 26 5 5 Maximum loading of circuit breakers 27 6 Functions and interfaces ...
Страница 3: ... Contents c 3 63 6 12 ready2mains 56 6 13 DC recognition 57 6 14 Dimming on DC only EXC3 58 6 15 Intelligent Temperature Guard 59 6 16 Surge Burst protection 61 7 Reference list 62 7 1 Additional information 62 7 2 Downloads 62 7 3 Technical data 63 ...
Страница 4: ... of information diagrams or descriptions in these instructions The latest version of these operating instructions is available on our home page at http www tridonic com com en operating instructions asp Copyright This documentation may not be changed expanded copied or passed to third parties without the prior written agreement of TRIDONIC GmbH Co KG We are always open to comments corrections and ...
Страница 5: ...evice may only be used for this intended purpose Improper use Outdoor use Extensions and modifications to the product Dangers associated with the operation of the system Environment WARNING Improper use could result in injury malfunction or damage to property It must be ensured that the operator informs every user of existing hazards DANGER Danger of electrocution Disconnect the power of the entir...
Страница 6: ...3 Additional instructions CAUTION Electromagnetic compatibility EMC Although the device meets the stringent requirements of the appropriate directives and standards on electromagnetic compatibility it could potentially interfere with other devices under certain circumstances ...
Страница 7: ... design The offer a safe and reliable solution under difficult weather and electrical LCO NFC C EXC3 and LCO NFC C ADV3 circumstances e g street and roadlight tunnel carpark _ Lifetime Excellent lifetime thanks to special design _ Safety Up to 10 kV surge burst protection _ Thermomanagement t up to 70 C with 65 000 hours lifetime a _ State of the art dimming technology Stepless dimming from 100 to...
Страница 8: ...ronoSTEP V2 inputDIM Dimming interfaces ADV3 chronoSTEP V2 inputDIM Functions Portfolio Description Intelligent Voltage Guard Intelligent Temperature Guard Power up Fading DC Operation DC level adjustable supporting EN 50172 eCLO Configuration Interfaces EXC3 NFC DALI V2 DT6 ready2mains U6Me2 Configuration Interfaces ADV3 NFC ready2mains Output current Portfolio Description Adjustable output curre...
Страница 9: ...Manual LCO EXC3 ADV3 OTD 03 2020 1 2 en Main values and functions c 9 63 Technical data Portfolio Description Rated supply voltage 220 240 V Standby losses 0 16 W ...
Страница 10: ...vailable in the following housing variants Image Description Housing variant compact Compact shape for installation inside the luminaire casing in built Typical area of application Road street industry _ Compact shape for installation inside the luminaire casing in built _ Typical area of application Road street industry _ Compact shape for installation inside the luminaire casing in built _ Typic...
Страница 11: ...LCO EXC3 ADV3 OTD 03 2020 1 2 en Housing variants c 11 63 Housing variant compact potted Compact shape for installation inside the luminaire casing in built _ Typical area of application Road street industry _ ...
Страница 12: ...on errors and events with the companionSUITE A correct communication between the LED Driver and the NFC antenna can only be guaranteed if the Driver is directly placed on the antenna Any material placed between the LED Driver and the NFC antenna can cause a deterioration of the communication quality We recommend the use of following NFC antennas www tridonic com nfc readers NFC is compliant with I...
Страница 13: ...of Value in LED module Value in LED Driver Detailed procedure 1 Current I HO rated Output current turn page Imax Output current tolerances The requirements for operating together can be checked by comparing the data sheets _ Subsequent practical tests can ensure that there are no unexpected problems during actual operation _ Determine forward current of module _ Check whether LED Driver can be ope...
Страница 14: ...AUTION The forward voltage is temperature dependent Refer to the Vf t diagram in the data sheet p I NOTICE To ensure full dimming performance the forward voltage of the LED module at min dim level must be greater than or equal to the min output voltage of the driver Determine the forward voltage of the LED module at lowest dim level _ In case there is no data available for the LED module at lowest...
Страница 15: ...m luminaire LED Driver components LED module wiring are coordinated and working properly Transient behaviour _ Colour shift _ Connection during operation _ Parasitic capacitance _ Flickering _ Stroboscopic effect video applications _ Dimming behaviour _ Colour change stability _ Luminous flux _ All tolerances _ Entire temperature range _ Different output voltage ranges incl no load _ Entire dimmin...
Страница 16: ...own here using two examples Example 1 Comparison data for LED Driver LED Driver Designation LCA 75W 250 750mA one4all C PRE OTD Manufacturer TRIDONIC Data sheet values of LED Driver Output current 700 mA Output current tolerance 3 Min output voltage 45 V 1 Max output voltage 107 V 1 Output LF current ripple 5 Max output current peak Output current 40 Output power 75 0 W 1 Values at 700 mA ...
Страница 17: ...et values of LED module Forward current 700 mA Max DC forward current 1400 mA Typ forward voltage 33 V 10 1 Min forward voltage 43 6 V 1 Max forward voltage 49 8 V 1 Max permissible LF current ripple 1800 mA Max permissible peak current 2 000 mA Power draw 32 14 W 1 Values at 700 mA Questions Is the LED Driver able to operate two modules _ Can the required luminous flux of 3 000 lm be achieved wit...
Страница 18: ...LED Driver can be set so that it delivers precisely this value of 700 mA as the output current _ The output current of the LED Driver including tolerances 700 mA 3 721 mA is less than or equal to the max DC forward current of the LED module 1400 mA _ The voltage range of the LED module 2 x 43 6 V 87 2 V 2 x 49 8 V 99 6 V lies completely within the voltage range of the LED Driver 45 107 V _ The Out...
Страница 19: ... Driver LED Driver Designation LCA 75W 250 750mA one4all C PRE OTD Manufacturer TRIDONIC Data sheet values of LED Driver Output current 700 mA Output current tolerance 3 Min output voltage 45 V 1 Max output voltage 107 V 1 Output LF current ripple 5 Max output current peak Output current 40 Output power 75 0 W 1 Values at 700 mA ...
Страница 20: ...alues of LED module Forward current 700 mA Max DC forward current 1 050 mA Typ forward voltage 39 5 V 10 1 Min forward voltage 35 55 V 1 Max forward voltage 43 45 V 1 Max permissible LF current ripple 630 mA Max permissible peak current 1 500 mA Power draw 19 75 W 1 Values at 700 mA Questions Are the two components mutually compatible _ Can the required luminous flux of 1 800 lm be achieved with t...
Страница 21: ...n be set so that it delivers precisely this value of 700 mA as the output current _ The output current of the LED Driver including tolerances 700 mA 3 721 mA is less than or equal to the max DC forward current of the LED module 1 050 mA _ The voltage range of the LED module 35 55 V 43 45 V is not within the voltage range of the LED Driver 45 V 107 V _ The Output LF current ripple 5 of output curre...
Страница 22: ...tructions of the lamp manufacturer _ Observe all relevant standards Follow the instructions given in the standards _ WARNING Comply with the general safety instructions see General safety instructions p 5 _ To avoid failures due to ground faults protect the wiring against mechanical loads from sharp edged metal parts e g cable penetrations cable holders metal frames etc _ LED Drivers from Tridonic...
Страница 23: ...tually eliminated by earthing the devices Avoiding the transfer of mains transients to the LED output The transfer of mains transients to the LED output presents a problem for many LED Driver topologies currently on the market and TRIDONIC devices may be affected Voltage peaks at the input of the LED Driver may be transferred to the output of the device where they lead to differences in potential ...
Страница 24: ...iver without earthing left and with earthing right I NOTICE Irrespective of whether the LED Driver is earthed or not LED modules must be insulated in accordance with the requirements of the luminaire protection class Improved insulation of the LED module can also reduce the likelihood of flashovers ...
Страница 25: ...d certainly not be used for routine testing Type testing Type testing of the luminaire is performed according to IEC 60598 1 Section 10 The wiring for protection class 1 luminaires is tested at a voltage of 2xU 1 000 V In order not to overload the LED Driver all the inputs and outputs of the LED Driver are connected to one another U is used for measuring the voltage for luminaires with LED Driver ...
Страница 26: ...e sensor _ Depending on the design of the luminaire it may be possible to improve the radio interference properties by earthing the device at the earth connection _ The LED Driver has no inverse polarity protection on the secondary side Wrong polarity can damage LED modules with no inverse polarity protection _ Use solid wire or stranded wire with the correct cross section _ Strip off correct leng...
Страница 27: ...eaker because of the summation of the different inrush currents The value is calculated through simulation programs based on the circuit breakers characteristic Information about the maximum loading can be found in Tridonic data sheets The following table shows the data for LCO as an example 60 200 1050 100 o4a NF C EXC3 Automatic circuit breaker type C10 C13 C16 C20 B10 B13 B16 B20 Inrush current...
Страница 28: ...rrent A Duration µs Calculation of the inrush current The inrush current of a control gear is also defined by its duration and its height The duration is typically measured as the time between 10 of maximum current ascending and 50 of maximum current descending The following illustration shows the inrush current of a single control gear I NOTICE Information about the specific tripping characterist...
Страница 29: ...ulation The above mentioned parameters height and duration of the current pulse in both the circuit breaker and the control gear are entered into the simulation program The result of the simulation is presented in graphical form The different elements have the following meaning Circuit breaker B10 B13 B16 B20 solid line represent the tripping characteristics of different circuit breakers _ ...
Страница 30: ...sents the result for 1 control gear point 2 the result for 2 control gear etc _ The crossing of the two lines shows the maximum value for the selected combination of circuit breaker and inrush current _ The index of the point at this maximum value shows the max number of control gear _ max 5 devices at circuit breaker B10 green tripping characteristic _ max 7 devices at circuit breaker B13 pink tr...
Страница 31: ... of the inrush current especially important Which electrolytic capacitor is installed in the control gear _ Considering a safety buffer Tridonic 20 for the electrolytic capacitor _ Considering different system impedance _ Switch on point used should always be at max input voltage _ Adopted cable lengths and cable data Tridonic Cable length 40 cm Resistivity 0 0172 ohm mm m inductance 5 nH 2 cm ter...
Страница 32: ...own to 10 Below 80 V input voltage the LED Driver shuts down restarts at 90 V without a reset and dims linearly up back to 100 Above 280 V input voltage the LED Driver shuts down If input voltage drops below 270 V the LED Driver restarts without a reset WARNING If the driver is operated on voltages higher 280V it will turn off automatically This is a safety feature only on streetlight a pplication...
Страница 33: ...vated by default Deactivating the IVG Plus function Deactivating the IVG Plus function via masterCONFIGURATOR valid only for EXC3 The eCLO function can be deactivated via the masterCONFIGURATOR Further information can be found in the masterCONFIGURATOR manual see http www tridonic com com en download Manual_masterConfigurator_en pdf ...
Страница 34: ... the output current of the LED Driver throughout its lifetime As a results a virtually uniform light output is achieved at all times Up to 8 steps each with a timer value and an intensity value can be used for the configuration Starting from these steps the control of the output current takes place automatically If the function visual feedback is enabled visual feedback is given as soon as the LED...
Страница 35: ...s LEDs with different burning hours can be matched to each other when LEDs are replaced 0 h 131 070 h Visual feedback Off If visual feedback is enabled visual feedback is given as soon as the LED exceeds the expected LED lamp life If the expected LED lamp life is exceeded the luminaire flashes for 2 seconds after being switched on Off On Commissioning Activating and adjusting the eCLO function Act...
Страница 36: ...el can be set individually within the voltage range stated above The input voltage regulation has higher priority than inputDIM If the min dimming level set by the inputDIM function is IVG Plus higher than the max allowed dimming level of IVG Plus the value of IVG Plus has priority Depending on the level of the input voltage the intensity of the LED can be set with two adjustable interpolation poi...
Страница 37: ...tDIM function via companionSUITE The inputDIM function can be activated and adjusted via companionSUITE Further information can be found on the Tridonic homepage at and http www tridonic com download help Overview_en html http www tridonic com download help corridorFUNCTION_en html Activating and adjusting the inputDIM function via masterCONFIGURATOR The inputDIM function can be activated and adju...
Страница 38: ...temperature exceeds the limit T3 critical temperature the device will switch to the shutdown level The shutdown level will be active until the module temperature decreases below T1 or until the LED Driver is restarted switch off or mains reset The allowed NTC resistor value is between 0 to 2 megaohm By default there are three predefined values that can be set via programming software up to five in...
Страница 39: ... defined values can be entered The sensor constant BETA and the resistance at 25 C R25 can be precisely defined NCP 18XH103J NCP 18XW153J NCP 18XW223J User defined Sensor constant BETA 0 K This constant is needed to convert the resistance value to a tempera ture in an NTC resistor displayed in Kelvin 0 K 4 890 K Resistance at 25 C R25 0 ohm Resistance value of the NTC sensor at 25 C 0 ohm 470 000 ...
Страница 40: ...ally the times at which the sun sets and rises The midpoint of these two reference points is the time referred to as Virtual Midnight To allow immediate operation in the first night it is possible to program the Virtual Midnight manually The overall time between switch ON and switch OFF is called On Time Overall there are 8 profiles 5 are predefined by factory and 3 can be programmed by the custom...
Страница 41: ...FUNCTION_en html Activating and adjusting the chronoSTEP V2 function via masterCONFIGURATOR The chronoSTEP V2 function can be activated and adjusted via the masterCONFIGURATOR Further information can be found in the masterCONFIGURATOR manual see http www tridonic com com en download Manual_masterConfigurator_en pdf Activating and adjusting the chronoSTEP V2 function via U6Me2 The chronoSTEP V2 fun...
Страница 42: ...ion type to activate and adapt the chronoSTEP function in the device using switch on and switch off commands Further information can be found in the chronoSTEP V2 Instruction manual U6Me2 programming see https www tridonic com com de download technical Instruction_manual_U6Me2_programming_en pdf ...
Страница 43: ... can provide the best possible performance in a range of conditions The profiles are defined by a series of values Fade in time the time that starts as soon as the presence of a person is detected During the fade in time the luminous intensity is faded up to the presence value default 0s Run on time the time that starts as soon as the presence of a person is no longer detected If the presence of a...
Страница 44: ...e LED Driver is correctly installed in the luminaire _ Input voltage is applied _ A motion sensor is connected to information DA N or DA L _ Remain in the activation range of the motion sensor for more than 5 minutes The motion sensor detects movement and switches on The corridorFUNCTION V2 is activated automatically after 5 minutes The light value switches to presence level default 100 _ Set the ...
Страница 45: ... www tridonic com com en download Manual_masterConfigurator_en pdf Activating and adjusting the corridorFUNCTION V2 via companionSUITE The corridorFUNCTION V2 can be activated and adjusted via companionSUITE Further information can be found on the Tridonic homepage at and http www tridonic com download help Overview_en html http www tridonic com download help corridorFUNCTION_en html Connect mains...
Страница 46: ...s correctly installed in the luminaire and cabled on the power supply side _ A motion sensor is installed in the lighting system _ The motion sensor is connected to the LED Driver _ Connect the neutral wire N to terminal DA N on the LED Driver _ Connect the output of the motion sensor switched phase to terminal DA L on the LED Driver _ ...
Страница 47: ...use glow switches Glow switches may affect the control CAUTION Make sure that the control line L of the motion sensor is connected to terminal DA L and the neutral wire N to terminal DA N CAUTION For five pole wiring the neutral wire must be connected to DA N This prevents 400 V being applied between adjacent terminals if a different phase is used for the control input I NOTICE For large installat...
Страница 48: ...ia masterCONFIGURATOR The DSI function can be activated and adjusted via the masterCONFIGURATOR Further information can be found in the masterCONFIGURATOR manual see http www tridonic com com en download Manual_masterConfigurator_en pdf Expansion options via submodules for example in combination with daylight control or additional switch modules _ Wiring Simple wiring with five pole standard cable...
Страница 49: ...ted via the masterCONFIGURATOR Further information can be found in the masterCONFIGURATOR manual see http www tridonic com com en download Manual_masterConfigurator_en pdf A short press 50 600 ms switches the device on or off _ A long press 600 ms fades the connected operating device alternately up and down between 1 and 100 _ CAUTION Glow switches are not approved for controlling switchDIM Glow s...
Страница 50: ...omatically switches to the corresponding operating mode Procedure Installation Wiring variants There are two options for installing switchDIM four pole and five pole wiring Switch the device on off by briefly actuating the push button or _ Dim the device by holding down the push button _ Hold down the push button for 10 seconds All devices will be synchronized to the same status LEDs will will be ...
Страница 51: ...d for a control line thanks to bridging terminal DA N and the N connection of the luminaire Five pole wiring Configuration Phase L neutral N earth PE control line L control line neutral N Benefits Control can be changed at any time to a digital control signal DSI or DALI without having to change the luminaire or provide an additional control line ...
Страница 52: ...TD 03 2020 1 2 en switchDIM c 52 63 CAUTION For five pole wiring the neutral conductor must be connected to DA N This prevents 400 V being applied between adjacent terminals if a different phase is used for the control input ...
Страница 53: ... programmed as a DALI fade time in the range from 0 7 to 16 seconds and dims in the selected time from 0 percent to the power on level By factory default power up fading is not active 0 seconds Commissioning Activating and adjusting Power up Fading via masterCONFIGURATOR The Power up Fading function can be activated and adjusted via the masterCONFIGURATOR Further information can be found in the ma...
Страница 54: ...mple light switch to lighting management systems for entire office complexes with thousands of light sources DALI in Action DALI offers a lot of possibilities Technical data of a DALI line I NOTICE LCO OTD devices support the new DALI standard V2 according to EN 62386 102 DALI line 64 control gear can be grouped to a line _ DALI groups Every control gear can be attributed into 16 groups _ Addressa...
Страница 55: ...masterCONFIGURATOR manual see http www tridonic com com en download Manual_masterConfigurator_en pdf eD eD enhanced DALI offers extended DALI commands They can be used to activate specific commands of the LED Driver The masterCONFIGURATOR software works with eD commands These commands are Tridonic specific They are not part of the DALI standard and are not publicly available I NOTICE If the corrid...
Страница 56: ...reduces production costs and installation costs and also reduces possible sources of error Configuration The ready2mains interface can be used to configure the main parameters of LED Drivers via the mains wiring LED output current CLO and DC level These parameters can be adjusted either via ready2mains capable configuration software or directly via the ready2mains programmer output current only Fu...
Страница 57: ...de and dims the light to the defined DC level Without DC recognition different and more complex solutions need to be applied in order to detect emergency mode LED Drivers of the LCO EXC ADV OTD series are factory preset to a DC level of 15 This value can be customized Further information can be found in the masterCONFIGURATOR manual see Reference list p 62 I NOTICE The LED Driver is designed to op...
Страница 58: ...und on the Tridonic homepage at and http www tridonic com download help Overview_en html http www tridonic com download help corridorFUNCTION_en html The present dimming level is retained _ An emergency light level defined for the DC recognition function DC level is ignored _ Control signals via DALI and DSI continue to be executed _ WARNING If Dimming on DC is activated the emergency mode is not ...
Страница 59: ...ith relevant standards The Intelligent Temperature Guard function does not replace the proper thermal design of the luminaire and does not enable the lighting to operate for lengthy periods of time in impermissible ambient temperatures I NOTICE The temperature at which the power reduction starts is device specific and depends on the load and the installation situation Depending on the installation...
Страница 60: ..._en pdf Activating and adjusting the ITG via companionSUITE The ITG function can also be activated and adjusted via companionSUITE Further information can be found on the Tridonic homepage at and http www tridonic com download help Overview_en html http www tridonic com download help corridorFUNCTION_en html Power reduction continues if temperature still rises _ Power reduction stops if temperatur...
Страница 61: ...with a 6 kV protection only 1 out of 10 luminaires are protected This better protection has clear advantages Bursts According to Standard IEC 61547 Ed 2 0 2009 tests are conducted according to IEC 61000 4 4 with test levels as given in Tables 4 to 6 Fast transients with positive and negative polarity are applied to the device for a minimum of 2 minutes each Surges Tests are conducted according to ...
Страница 62: ... pdf _ Documentation masterCONFIGURATOR http www tridonic com com en download Manual_masterConfigurator_en pdf _ Leaflet Outdoor http www tridonic com com en download brochures Leaflet_Outdoor_EN_web pdf _ Leaflet ready2mains http www tridonic com com en download brochures Leaflet_ready2mains_EN_web pdf _ Product manual ready2mains Programmer http www tridonic com com en download technical ready2m...
Страница 63: ...ental declarations asp _ LED lamp matrix http www tridonic com com en lamp matrix asp _ Operating instructions http www tridonic com com en operating instructions asp _ Other technical documents http www tridonic com com en technical docs asp _ Tender text http www tridonic com com en tender asp _ Declarations of conformity Available documents are found on each product page of our website in the C...