Object Instance
Functional Description
Read or Write
Analog Inputs
AI - 1
Analog Input 1 (default: Primary Room Pressure)
Read-Only
AI - 17
Analog Input 2 (default: Secondary Room Pressure)
Read-Only
AI - 18
Analog Input 3 (default: Relative Humidity)
Read-Only
AI - 19
Analog Input 4 (default: Supply/Exhaust Flow)
Read-Only
AI - 20
Thermistor Input 1 (default: Room Temperature)
Read-Only
AI - 21
Thermistor Input 2 (default: spare temperature input)
Read-Only
Analog Outputs
AO - 1
Analog Output 1 (default: Primary Exhaust Damper Control)
Read-Only
AO - 11
Analog Output 2 (default: Supply/Exhaust Damper Control)
Read-Only
AO - 12
Analog Output 3 (spare control output)
Read-Only
AO - 13
Analog Output 4 (spare control output)
Read-Only
Binary Inputs
BI - 3
Digital Input 1 (default: Primary Room Door Switch)
Read-Only
BI - 4
Digital Input 2 (default: Secondary Room Door Switch)
Read-Only
BI - 5
Digital Input 3 (spare digital input)
Read-Only
BI - 6
Digital Input 4 (spare digital input)
Read-Only
Binary Outputs
BO - 1
Relay Output 1 (default: Primary Alarm Relay Output)
Read-Only
BO - 2
Relay Output 2 (spare relay output)
Read-Only
BO - 3
Relay Output 3 (spare relay output)
Read-Only
BO - 4
Relay Output 4 (spare relay output)
Read-Only
Internal Float Values
ADF - 1
PID Control Loop 1 Setpoint (Primary Differential Pressure)
Read/Write
ADF - 2
Primary Room Alarm Relay High Setpoint
Read/Write
ADF - 3
Primary Room Alarm Relay Low Setpoint
Read/Write
ADF - 4
Secondary Room Alarm Relay High Setpoint
Read/Write
ADF - 5
Secondary Room Alarm Relay Low Setpoint
Read/Write
ADF - 8
Primary Room Low Alarm Setpoint
Read/Write
ADF - 9
Primary Room Low Warning Setpoint
Read/Write
ADF - 10
Primary Room High Warning Setpoint
Read/Write
ADF - 11
Primary Room High Alarm Setpoint
Read/Write
ADF - 13
PID Control Loop 2 Setpoint
Read/Write
ADF - 14
PID Control Loop 3 Setpoint
Read/Write
ADF - 15
PID Control Loop 4 Setpoint
Read/Write
ADF - 16
Air Change Rate based on Flow Input at AI-1
Read-Only
ADF - 17
Air Change Rate based on Flow Input at AI-2
Read-Only
ADF - 18
Air Change Rate based on Flow Input at AI-3
Read-Only
ADF - 19
Air Change Rate based on Flow Input at AI-4
Read-Only
ADF - 20
Alarm Relay 3 High Setpoint
Read/Write
ADF - 21
Alarm Relay 3 Low Setpoint
Read/Write
ADF - 22
Alarm Relay 4 High Setpoint
Read/Write
ADF - 23
Alarm Relay 4 Low Setpoint
Read/Write
ADF - 24
AI-2 Low Alarm Setpoint
Read/Write
ADF - 25
AI-2 Low Warning Setpoint
Read/Write
ADF - 26
AI-2 High Warning Setpoint
Read/Write
METASYS N2 OBJECTS
FMS-1655
-
48
-
Metasys
®
N2 Objects
Triatek reserves the right to change product specifications without notice.
Содержание FMS-1655
Страница 1: ...FMS 1655 Installation Manual Version 11 15 16 Triatek FMS 1655 Room Pressure Controller ...
Страница 2: ...FMS 1655 Triatek reserves the right to change product specifications without notice Notes ...
Страница 27: ...MOUNTING WIRING FMS 1655 Triatek reserves the right to change product specifications without notice 20 Notes ...
Страница 49: ...FMS 1655 42 QUICK START GUIDE Notes Triatek reserves the right to change product specifications without notice ...
Страница 57: ...FMS 1655 50 Notes Triatek reserves the right to change product specifications without notice ...
Страница 63: ...Notes FMS 1655 56 Triatek reserves the right to change product specifications without notice ...