SUBHEAD
FMS-1655
-
47
-
BACnet OBJECTS
Triatek reserves the right to change product specifications without notice.
Object Instance
Functional Description
Read or Write
AV - 20
AI-1 Low Warning Setpoint (low differential pressure warning)
Read/Write
AV - 21
AI-1 High Warning Setpoint (high differential pressure warning)
Read/Write
AV - 22
AI-1 High Alarm Setpoint (high differential pressure alarm)
Read/Write
AV - 23
AI-2 Low Alarm Setpoint
Read/Write
AV - 24
AI-2 Low Warning Setpoint
Read/Write
AV - 25
AI-2 High Warning Setpoint
Read/Write
AV - 26
AI-2 High Alarm Setpoint
Read/Write
AV - 27
AI-3 Low Alarm Setpoint
Read/Write
AV - 28
AI-3 Low Warning Setpoint
Read/Write
AV - 29
AI-3 High Warning Setpoint
Read/Write
AV - 30
AI-3 High Alarm Setpoint
Read/Write
AV - 31
AI-4 Low Alarm Setpoint
Read/Write
AV - 32
AI-4 Low Warning Setpoint
Read/Write
AV - 33
AI-4 High Warning Setpoint
Read/Write
AV - 34
AI-4 High Alarm Setpoint
Read/Write
AV - 35
TI-1 Low Alarm Setpoint
Read/Write
AV - 36
TI-1 Low Warning Setpoint
Read/Write
AV - 37
TI-1 High Warning Setpoint
Read/Write
AV - 38
TI-1 High Alarm Setpoint
Read/Write
AV - 39
TI-2 Low Alarm Setpoint
Read/Write
AV - 40
TI-2 Low Warning Setpoint
Read/Write
AV - 41
TI-2 High Warning Setpoint
Read/Write
AV - 42
TI-2 High Alarm Setpoint
Read/Write
AV - 43
Writable Network Variable – Humidity
Read/Write
AV - 44
Writable Network Variable – Temperature
Read/Write
AV - 45
Writable Network Variable – Air Changes
Read/Write
AV - 46
Writable Network Variable – Differential Pressure
Read/Write
AV - 47
Device ID Offset (range: 0 – 4,194,000)
Read/Write
AV - 48
Duct Air Flow based on AI-1 flow input
Read-Only
AV - 49
Duct Air Flow based on AI-2 flow input
Read-Only
AV - 50
Duct Air Flow based on AI-3 flow input (Supply Flow)
Read-Only
AV - 51
Duct Air Flow based on AI-4 flow input (Exhaust Flow)
Read-Only
AV - 52
Volumetric Offset (Supply Flow – Exhaust Flow)
Read-Only
AV - 53
Volumetric Offset Setpoint
Read-Write
AV - 54
AO-1 Override Level
Read-Write
AV - 55
AO-2 Override Level
Read-Write
AV - 56
AO-3 Override Level
Read-Write
AV - 57
AO-4 Override Level
Read-Write
AV - 58
AI-1 Deadband Setting
Read-Write
AV - 59
AI-2 Deadband Setting
Read-Write
AV - 60
AI-3 Deadband Setting
Read-Write
AV - 61
AI-4 Deadband Setting
Read-Write
AV - 62
TI-1 Deadband Setting
Read-Write
AV - 63
TI-2 Deadband Setting
Read-Write
Multistate Objects
MSO - 1
Primary Room Isolation Mode: 1=positive, 2=negative, 3=neutral
Read-Write
MSO - 2
Secondary Room Isolation Mode: 1=positive, 2=negative, 3=neutral
Read-Write
Triatek reserves the right to change product specifications without notice.
BACnet
®
Objects
Содержание FMS-1655
Страница 1: ...FMS 1655 Installation Manual Version 11 15 16 Triatek FMS 1655 Room Pressure Controller ...
Страница 2: ...FMS 1655 Triatek reserves the right to change product specifications without notice Notes ...
Страница 27: ...MOUNTING WIRING FMS 1655 Triatek reserves the right to change product specifications without notice 20 Notes ...
Страница 49: ...FMS 1655 42 QUICK START GUIDE Notes Triatek reserves the right to change product specifications without notice ...
Страница 57: ...FMS 1655 50 Notes Triatek reserves the right to change product specifications without notice ...
Страница 63: ...Notes FMS 1655 56 Triatek reserves the right to change product specifications without notice ...