background image

QUICK START GUIDE

FMS-1655

40

 -

revert to the yellow graphical caution screen 

whenever the door is open and the unit is 

not in neutral isolation mode. Once the door 

closes, the door delay will count down, and 

then release the suspended control output 

once it expires. 

Setting Up Alarm Relay Output

When the alarm status must be transmitted to 

a remote location, like a nurses’ station, the 

alarm relay output can be configured using 

the following procedure. Select 

Unit Setup

 

Controller Setup

 > 

Relay Setup

 and the 

user is prompted to select the trigger mode 

(setpoints, isolation mode, or occupancy 

mode). The default trigger mode is 

Setpoints

which allows the alarm relay to be activated 

based on exceeding setpoint limits entered 

by the user. 

Isolation Mode

 and 

Occupancy 

Mode

 allow the alarm relay to be activated 

based on a change in the mode of isolation 

and state of occupancy, respectively. Once 

the relay trigger mode is selected, the user 

is prompted to enter the high and low relay 

setpoints using the sliders on the popup 

screen. Finally, the operating mode (direct or 

reverse acting) must be specified along with 

a delay time. The delay time determines how 

long the alarm relay output is delayed before 

being activated after one of the relay setpoint 

limits has been exceeded. The default setting 

for the delay time is zero seconds. 

Setting Alarm Limits

To determine the limits at which the unit status 

changes from normal to warning, and from 

warning to alarm, the alarm limits must be 

configured as follows. Select 

Unit Setup

 > 

Controller Setup

 > 

Alarm Limits

 and the user 

is prompted to specify the high and low alarm 

and warning limits. These limits should be 

specified to set the differential pressure range 

which is considered normal, as well as the 

range which indicates a warning condition, 

and the range which is considered critical and 

indicates an alarm condition.

Changing Isolation Mode

The FMS-1655 isolation room controller 

may be configured for 

Positive

Negative

, or 

Neutral

 modes of isolation. To change the 

mode of isolation, select 

Unit Setup

 > 

Room 

Setup

 > 

Isolation Mode 

and select one of 

three isolation modes, or 

Auto Clean

 mode. 

Auto Clean

 mode automates the turnover of 

an isolation room that has been vacated in 

preparation for the next occupant. For those 

states or locales that have code restrictions 

regarding the accessible modes of isolation, 

the unit may be configured to allow either 

Positive

 and 

Neutral

 or 

Negative

 and 

Neutral

 

modes. Changing the mode of isolation 

automatically selects the pre-programmed 

setpoints and alarm limits associated with 

each mode.

Invoking Auto Clean Cycle

When an isolation room has been vacated, it 

must be cleaned of all airborne contaminants 

before the next patient may occupy the room. 

The FMS-1655 includes a convenient feature 

called 

Auto Clean Cycle

 that automates the 

turnover process and cleaning of the room. 

Auto Clean Cycle

 may be invoked using 

one of two methods, either from the 

Status

 

hotspot on the main display screen or from 

the 

Isolation Mode

 option on the 

Isolation 

Room Setup

 menu. Invoking 

Auto Clean 

Cycle

 automatically commands the exhaust 

valve or damper for maximum flow for the 

configured duration to facilitate the removal of 

all airborne contaminants. If the Safety Halo

TM

 

status bezel has been enabled, it will flash 

in cyan color to indicate that an 

Auto Clean 

Cycle

 is in progress. When the Auto Clean 

Cycle is completed, a message will appear 

on the main display screen indicating that the 

monitored room was successfully cleaned 

and is available for use. The Safety Halo

TM

 

will stop flashing but remain cyan until this 

message is acknowledged by the user.

Changing Network Settings

Changing network settings on the FMS-1655 

can be accessed by selecting 

Unit Setup

 > 

Network Setup

. Depending upon the protocol 

selected, the Network Setup menu will 

present the user with the available options. All 

FMS-1655 demo units have a default protocol 

selection of BACnet, and therefore the 

Network Setup

 menu options pertain to this 

protocol. From this menu, the user can select 

a different baud rate or change the network 

address of the unit.

Adding Password Security

The FMS-1655 menu system can be 

protected by adding up to ten (10) multi-level 

passwords to the system. A password entry 

may be created by selecting 

System Setup 

Next

 > 

Passwords Setup

 > 

Add Password 

and the user is prompted to enter a minimum 

of four (4) and up to eight (8) digits. Once 

a password has been specified, the user is 

prompted to specify one of four access levels: 

Unrestricted

Standard

Basic

, and 

Restricted

All password entries are saved to non-volatile 

memory. If a password is forgotten, there is a 

factory-default “back door” password that will 

provide unrestricted access to the user menu 

system. Please consult with the factory for 

more information regarding this password.

Note: The first user password is 

automatically saved as unrestricted. 

Changing Display Settings

The Safety Halo™ feature is exclusive to the 

1655 series of controllers from Triatek, and 

FMS-1655 Quick Start Guide

Triatek reserves the right to change product specifications without notice.

Содержание FMS-1655

Страница 1: ...FMS 1655 Installation Manual Version 11 15 16 Triatek FMS 1655 Room Pressure Controller ...

Страница 2: ...FMS 1655 Triatek reserves the right to change product specifications without notice Notes ...

Страница 3: ...to follow the wiring diagrams could result in damage to your equipment and could void your warranty Wiring diagrams can also be found at www triatek com Under no circumstances should a single transformer be split between actuator and controller Doing so will damage the actuator the transformer the controller or all units A single 120 24V 30Va transformer is required for the controller and a separa...

Страница 4: ...ange zero based or offset Sensor Pressure Range Positive Isolation Setpoint Negative Isolation Setpoint Neutral Isolation Setpoint Pressure Deadband Analog Output Operating Mode Direct or PID Analog Output Range zero based or offset Analog Output Upper Limit 0 100 Analog Output Lower Limit 0 100 Analog Output Input Channel AI 1 thru AI 4 TI 1 or TI 2 Analog Output Action Direct or Reverse Analog O...

Страница 5: ... Isolation High Warning Setpoint Positive Isolation Low Warning Setpoint Positive Isolation Low Alarm Setpoint Negative Isolation High Alarm Setpoint Negative Isolation High Warning Setpoint Negative Isolation Low Warning Setpoint Negative Isolation Low Alarm Setpoint Audible Alert Enabled Input Channels AI 1 thru AI 4 TI 1 TI 2 Operating Mode audible or silent Delay Time Base secs or mins Delay S...

Страница 6: ...stration 21 Analog Input to 2 Remote Pressure Sensors 0 10V Out Illustration 22 Analog Input to 2 Remote Pressure Sensor 4 20mA Out Illustration 23 Analog Input to 3 Remote Pressure Sensor 4 20mA Out Illustration 24 Analog Input to 4 Remote Pressure Sensor 4 20mA Out Illustration 25 Analog Input to Temperature Sensor Illustration 26 Digital Input to Door Switch Illustration 28 Digital Input to Flo...

Страница 7: ...net OBJECTS Analog Input Objects 48 Analog Output Objects 48 Binary Input Objects 48 Binary Output Objects 48 Analog Value Objects 48 49 Multistate Output Objects 49 METASYS N2 OBJECTS Analog Input Objects 50 Analog Output Objects 50 Binary Input Objects 50 Binary Output Objects 50 Internal Float Value Objects 50 51 Multistate Output Objects 51 CLEANING THE DISPLAY Cleaning the FMS 1655 53 DIAGRAM...

Страница 8: ...s N2 network Two Wire Twisted Pair RS 485 signaling Recommended Cable Type Belden 3107A Touchscreen User Interface LCD Size 3 2 diagonal LCD Type Transmissive Resolution 240 x 320 portrait Viewing Area 50 60 mm x 66 80 mm Color Depth 18 bit or 262K colors Backlight Color White Luminous Intensity Min 2500 cd m2 Recommended Cable Type applicable to surface mount models FMS 1655 s x only Belden 3125A...

Страница 9: ...n warns that changes or modifications to the unit not expressly approved by the part responsible for compliance could void the user s authority to operate the equipment This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions This device may not cause harmful interference and This device must accept any interference received including interference tha...

Страница 10: ... very intuitive and simplifies the setup and configuration of the unit The menus incorporate touch based interfaces such as sliders radio buttons and dialog popups to facilitate the ease of use of the FMS 1655 The display implements bright graphical color changes to indicate the three different alarm status indications of the monitored isolation room These graphical backgrounds indicate Normal whe...

Страница 11: ...nel may have unrestricted access while general staff may be assigned restricted access passwords which limit the functionality of the user menus Room pressure selection of positive negative or neutral isolation may be protected using limited access passwords thereby eliminating the need for keylock switches and keys An optional keylock switch may be used to further control access to change in isol...

Страница 12: ...hscreen is easily accessible to facilitate silencing the unit in the event of an alarm The FMS 1655 is pre configured at the factory with the Safety Halo status indicator bezel connected to the internal circuitry on the display board and has been tested for proper operation The Safety Halo should not be removed from the flush mount faceplate as it may damage the internal circuitry and or the bezel...

Страница 13: ...opriate hardware 8 Mount the louvered stainless steel cover plate to the mounting plate with the screws supplied 9 Apply power to the FMS 1655 and confirm that following a brief initialization sequence the unit displays the room differential pressure and the Safety Halo status matches that of the main display screen FMS 1655 units are shipped from the factory in neutral isolation mode MOUNTING WIR...

Страница 14: ...ttings programmed in the factory according to the customer specifications The user can change the settings by using the instructions provided in the Quick Start section of this manual beginning on page 38 Triatek reserves the right to change product specifications without notice ...

Страница 15: ... 8 FMS 1655 MOUNTING WIRING Triatek reserves the right to change product specifications without notice Notes Triatek reserves the right to change product specifications without notice ...

Страница 16: ...inal hole dimensions are 3 65 H x 2 15 W 2 Drill a 7 16 hole through the opposite wall for the flow tube as shown 3 Bring the 3 conductor signal wire through the cut out 4 Install the included low voltage mounting bracket in the drywall opening and pull the 3 conductor signal cable through the mounting bracket 5 Push a length of flow tube through the back hole on through the 7 16 hole in the oppos...

Страница 17: ...ply around tube and between stainless steel plate and wall to seal unit penetration Terminal For connection of transmitter to FMS 1655 Flow Tube When Flow Tube mounting plate is located directly opposite the sensor flow tubing must be cut as short as possible to prevent kinks To FMS 1655 Controller Wall Section cutaway view Orange wall bracket to be installed first by using the rotating clamps for...

Страница 18: ...ounting Plate Gasket Thin Silicone Caulking apply around tube and between stainless steel plate and wall to seal unit penetration Terminal For connection of transmitter to FMS 1655 Flow Tube When Flow Tube mounting plate is located directly opposite the sensor flow tubing must be cut as short as possible to prevent kinks To FMS 1655 Controller Wall Section cutaway view Rotating clamps secure assem...

Страница 19: ...s the line voltage or other conductors that supply highly inductive loads such as generators motors solenoids contactors etc Use 22AWG or larger MOUNTING WIRING Triatek reserves the right to change product specifications without notice Remote Sensor Configuration Controller Configuration Dipswitch Settings S1 1 ON S1 5 OFF AI 1 set at 4 20mA Input Recommended 4 conductor connection Belden 1325A St...

Страница 20: ... to change product specifications without notice Analog Output to Electric Damper Actuator Controller Configuration Dipswitch Settings S1 2 ON S1 6 OFF AI 2 set as 4 20mA Input S4 1 ON AO 1 set as Voltage Output Step Down Isolation Transformer provided with FMS Controller ...

Страница 21: ...roduct specifications without notice Analog Output to Pneumatic Damper Actuator Controller Configuration Dipswitch Settings S1 2 ON S1 6 OFF AI 2 set as 4 20mA Input S4 1 ON AO 1 set as Voltage Output Step Down Isolation Transformer provided with FMS Controller Optional remote sensor ...

Страница 22: ...e product specifications without notice Analog Output to Variable Speed Drive Controller Configuration Dipswitch Settings S1 2 ON S1 6 OFF AI 2 set as 4 20mA Input S4 1 ON AO 1 set as Voltage Output Step Down Isolation Transformer provided with FMS Controller Optional remote sensor ...

Страница 23: ...uct specifications without notice Analog Output to Modulated Air Controller Controller Configuration Dipswitch Settings S1 2 ON S1 6 OFF AI 2 set as 4 20mA Input S1 4 ON S1 8 OFF AI 4 set as 4 20mA Input Step Down Isolation Transformer provided with FMS Controller Optional remote sensor ...

Страница 24: ... to change product specifications without notice Analog Output to Pneumatic Damper Actuator Controller Configuration Dipswitch Settings S1 1 ON S1 5 OFF AI 1 set as 20mA Input S4 1 ON AO 1 set as Voltage Output Step Down Isolation Transformer provided with FMS Controller ...

Страница 25: ...ht to change product specifications without notice Analog Output to Variable Speed Drive Controller Configuration Dipswitch Settings S1 1 ON S1 5 OFF AI 1 set as 20mA Input S4 1 ON AO 1 set as Voltage Output Step Down Isolation Transformer provided with FMS Controller ...

Страница 26: ...ge product specifications without notice 19 Controller Configuration Dipswitch Settings S1 2 ON S1 6 OFF AI 2 set as 4 20mA Input Adding Remote Pressure Sensor with 4 20mA Out to Internal Sensor Model Step Down Isolation Transformer provided with FMS Controller ...

Страница 27: ...MOUNTING WIRING FMS 1655 Triatek reserves the right to change product specifications without notice 20 Notes ...

Страница 28: ...pecifications without notice 21 Controller Configuration Dipswitch Settings S1 1 ON S1 5 OFF AI 1 set as 4 20mA Input S1 2 ON S1 6 OFF AI 2 set as 4 20mA Input Analog Input to 2 Remote Pressure Sensors 4 20mA Out Step Down Isolation Transformer provided with FMS Controller ...

Страница 29: ...onfiguration Dipswitch Settings S1 1 ON S1 5 OFF AI 1 set as 4 20mA Input S1 2 ON S1 6 OFF AI 2 set as 4 20mA Input S1 3 ON S1 7 OFF AI 3 set as 4 20 mA Input Triatek reserves the right to change product specifications without notice Step Down Isolation Transformer provided with FMS Controller ...

Страница 30: ...nge product specifications without notice Controller Configuration Dipswitch Settings S1 1 ON S1 5 OFF AI 1 set as 4 20mA Input S1 2 ON S1 6 OFF AI 2 set as 4 20mA Input S1 3 ON S1 7 OFF AI 3 set as 4 20 mA Input S1 4 ON S1 8 OFF AI 4 set as 4 20 mA Input Step Down Isolation Transformer provided with FMS Controller ...

Страница 31: ...specifications without notice 24 Analog Input to Temperature Sensor The above example associates the Thermistor with contacts T1 and AGND for illustrative purposes only In fact either of the two T s can be used Step Down Isolation Transformer provided with FMS Controller ...

Страница 32: ...ote Sensor FMS 1655 25 Triatek reserves the right to change product specifications without notice Controller Configuration Dipswitch Settings S1 2 OFF S1 6 ON AI 2 set as 0 10V Input Step Down Isolation Transformer provided with FMS Controller ...

Страница 33: ...0 may be purchased from Triatek for this specific purpose After the switch has been installed at the door and connected to the FMS unit its operation may be programmed as described on page 39 Controller Configuration Slideswitch Settings S5 Left Active Low Digital Input Digital Input to Door Switch Triatek reserves the right to change product specifications without notice Step Down Isolation Trans...

Страница 34: ...SUBHEAD FMS 1655 27 MOUNTING WIRING Triatek reserves the right to change product specifications without notice Notes ...

Страница 35: ...al Input to Occupancy Sensor Triatek reserves the right to change product specifications without notice The above example associates the Occupancy Sensor with contacts DI4 and DGND for illustrative purposes only In fact any of the four DI s can be used Step Down Isolation Transformer provided with FMS Controller ...

Страница 36: ...ecifications without notice Relay Output to Alarm The above example associates Monitor Output 1 with contacts RL3 and RL3_C for illustrative purposes only In fact any of the four RL s and the corresponding RL _C can be used Step Down Isolation Transformer provided with FMS Controller ...

Страница 37: ...o change product specifications without notice The above example associates Monitor Output 2 with contacts RL4 and RL4_C for illustrative purposes only In fact any of the four RL s and the corresponding RL _C can be used Step Down Isolation Transformer provided with FMS Controller ...

Страница 38: ...t specifications without notice Relay Output 1 The above example associates Heating State 1 with contacts RL1 and RL1_C for illustrative purposes only In fact any of the four RL s and the corresponding RL _C can be used Step Down Isolation Transformer provided with FMS Controller ...

Страница 39: ...ange product specifications without notice The above example associates Heating State 2 with contacts RL2 and RL2_C for illustrative purposes only In fact any of the four RL s and the corresponding RL _C can be used Step Down Isolation Transformer provided with FMS Controller ...

Страница 40: ...SUBHEAD FMS 1655 33 MOUNTING WIRING Triatek reserves the right to change product specifications without notice Power Step Down Isolation Transformer provided with FMS Controller ...

Страница 41: ...rovided with FMS 1655 Only Class 2 wiring in this compartment Note This product should be installed with the manufacturer provided isolated power supply and connected to an electrical circuit protected by a minimum 20A circuit breaker This circuit breaker should be mounted in an approved electrical enclosure located separately but in close proximity to this product 240 VAC 50 60 Hz Blue 1 Amp Slow...

Страница 42: ...SUBHEAD FMS 1655 35 MOUNTING WIRING Triatek reserves the right to change product specifications without notice Notes ...

Страница 43: ...ht to change product specifications without notice Controller Configuration Dipswitch Settings S3 7 ON S3 8 ON BACnet MS TP protocol selected NOTE For optimum network communications the reference signal REF must be connected to the BMS NETWK REF terminals at the backplane ...

Страница 44: ...ON S3 8 OFF Metasys N2 Open protocol selected COMMUNICATIONS Metasys N2 Open Triatek reserves the right to change product specifications without notice NOTE For optimum network communications the reference signal REF must be connected to the NETWK REF terminals at the backplane ...

Страница 45: ...ckmark at the center indicates that the current differential pressure is within allowable limits of the desired setpoint A yellow graphical background with an exclamation point at the center indicates one of two conditions 1 door to the monitored space is open if door switch is enabled or 2 the current differential pressure has drifted outside the allowable limits of the desired setpoint and is in...

Страница 46: ...p Analog Output and the user is prompted to select an operating mode direct control or PID control and an operating range Most applications will take advantage of the PID proportional integral derivative control mode where the control output can be customized by varying the control loop constants The operating range can either include an offset from zero or not independent of whether the analog ou...

Страница 47: ...des Changing the mode of isolation automatically selects the pre programmed setpoints and alarm limits associated with each mode Invoking Auto Clean Cycle When an isolation room has been vacated it must be cleaned of all airborne contaminants before the next patient may occupy the room The FMS 1655 includes a convenient feature called Auto Clean Cycle that automates the turnover process and cleani...

Страница 48: ...ID control loop if enabled Cancelling the override effectively resumes the normal PID control loop operation again if enabled A unique feature of the FMS 1655 is the Real Time View option which allows the user to see in real time the actual inputs and outputs along with their voltage levels or states One of the most useful tools for fine tuning the PID loop performance is the Analog I O Pairs scre...

Страница 49: ...FMS 1655 42 QUICK START GUIDE Notes Triatek reserves the right to change product specifications without notice ...

Страница 50: ...itch S2 mode configuration 1 1 Product Type OFF FMS HMS ON CMS 1655 2 Remote Display OFF Disabled ON Enabled 3 Mode Select OFF FMS 1655 CMS 1655 ON HMS 1655 4 Operational Mode OFF Demo Mode ON Run Mode Pushbutton Switch SW1 Reset Button Pushbutton Switch SW2 Reserved SUBHEAD FMS 1655 43 MODULE SETTINGS Triatek reserves the right to change product specifications without notice Configuring Display M...

Страница 51: ...tion 5 to OFF To configure FMS 1655 for a remote sensor set dipswitch position 1 to ON and dipswitch position 5 to OFF For other inputs see Table 1 Analog Output Configuration Dipswitch S3 1 AO 1 Mode Selection OFF current output ON voltage output 2 AO 2 Mode Selection OFF current output ON voltage output 3 AO 3 Mode Selection OFF current output ON voltage output 4 AO 4 Mode Selection OFF current ...

Страница 52: ...2 Protocol Selection Settings S3 Protocol Selection S3 7 S3 8 Reserved OFF OFF Metasys N2 ON OFF BACnet MS TP default ON ON Controller Configuration Dipswitch S4 1 AO 1 Voltage Range Selection OFF 0 10Vdc ON 0 5Vdc 2 AO 2 Voltage Range Selection OFF 0 10Vdc ON 0 5Vdc 3 AO 3 Voltage Range Selection OFF 0 10Vdc ON 0 5 Vdc 4 AO 4 Voltage Range Selection OFF 0 10Vdc ON 0 5 Vdc Controller Configuration...

Страница 53: ...gital input Read Only Binary Outputs BO 1 Relay Output 1 default Primary Alarm Relay Output Read Only BO 2 Relay Output 2 default Secondary Alarm Relay Output Read Only BO 3 Relay Output 3 spare relay output Read Only BO 4 Relay Output 4 spare relay output Read Only Analog Values AV 1 AI 1 Setpoint Isolation Room Differential Pressure Read Write AV 2 AI 2 Setpoint Anteroom Differential Pressure Re...

Страница 54: ...AV 41 TI 2 High Warning Setpoint Read Write AV 42 TI 2 High Alarm Setpoint Read Write AV 43 Writable Network Variable Humidity Read Write AV 44 Writable Network Variable Temperature Read Write AV 45 Writable Network Variable Air Changes Read Write AV 46 Writable Network Variable Differential Pressure Read Write AV 47 Device ID Offset range 0 4 194 000 Read Write AV 48 Duct Air Flow based on AI 1 f...

Страница 55: ... Read Only Internal Float Values ADF 1 PID Control Loop 1 Setpoint Primary Differential Pressure Read Write ADF 2 Primary Room Alarm Relay High Setpoint Read Write ADF 3 Primary Room Alarm Relay Low Setpoint Read Write ADF 4 Secondary Room Alarm Relay High Setpoint Read Write ADF 5 Secondary Room Alarm Relay Low Setpoint Read Write ADF 8 Primary Room Low Alarm Setpoint Read Write ADF 9 Primary Roo...

Страница 56: ... 49 Air Flow based on Flow Input at AI 2 Read Only ADF 50 Air Flow based on Flow Input at AI 3 default Supply Flow Read Only ADF 51 Air Flow based on Flow Input at AI 4 default Exhaust Flow Read Only ADF 52 Volumetric Offset Supply Flow Exhaust Flow Read Only ADF 53 Volumetric Offset Setpoint Read Write ADF 54 AO 1 Override Level Read Write ADF 55 AO 2 Override Level Read Write ADF 56 AO 3 Overrid...

Страница 57: ...FMS 1655 50 Notes Triatek reserves the right to change product specifications without notice ...

Страница 58: ... the monitored room Touching the current displayed pressure reading brings up the secondary pressure reading if the unit is in dual sensor mode Touching anywhere else on the screen enters the Main Setup Menu if no password is stored Otherwise a password must be entered before the Main Setup Menu can be accessed Touching DATE brings up the Date Entry popup to quickly change the current displayed da...

Страница 59: ...ve Wiring Diagram FMS 1655 52 Triatek reserves the right to change product specifications without notice Recommended 4 conductor connection Belden 3107A Step Down Isolation Transformer provided with FMS Controller ...

Страница 60: ...Integrated Flush Mount Wiring Box Dimensions FMS 1655 53 Triatek reserves the right to change product specifications without notice ...

Страница 61: ...Flush Mount Bracket Dimensions FMS 1655 54 Triatek reserves the right to change product specifications without notice ...

Страница 62: ...Thin Mount Wiring Box Dimensions FMS 1655 55 Triatek reserves the right to change product specifications without notice ...

Страница 63: ...Notes FMS 1655 56 Triatek reserves the right to change product specifications without notice ...

Страница 64: ...FLOW DIAGRAMS FMS 1655 57 Unit Setup Menu Tree Triatek reserves the right to change product specifications without notice ...

Страница 65: ...FLOW DIAGRAMS System Setup Menu Tree FMS 1655 58 Triatek reserves the right to change product specifications without notice ...

Страница 66: ...System Setup Menu Tree FLOW DIAGRAMS FMS 1655 Triatek reserves the right to change product specifications without notice 59 ...

Страница 67: ...FLOW DIAGRAMS FMS 1655 60 System Setup Menu Tree Triatek reserves the right to change product specifications without notice ...

Страница 68: ...FMS 1655 Due to continuous improvement Triatek reserves the right to change product specifications without notice 61 Display Setup Menu Tree Triatek reserves the right to change product specifications without notice ...

Страница 69: ...FLOW DIAGRAMS FMS 1655 62 Diagnostics Menu Tree Triatek reserves the right to change product specifications without notice ...

Страница 70: ...rs sensors actuators and more all designed to seamlessly integrate into a facility s building automation system Laboratories Classrooms Vivariums Hospitals Triatek s customer service is unparalleled Our product support system includes on site installations phone support repairs calibrations and in depth training sessions From our knowledgeable engineers and sales team to our talented field technic...

Отзывы: