10
-
FMS-1655
FMS-1655 with Standard Remote Sensor (9-Pin)
NC NC GND NC NC Io NC GND +V
in
NC NC GND NC NC Io NC GND +V
in
~~
~ ~
Standard Remote Sensor Detail
(Side View)
ISOLATION
ROOM
CORRIDOR
Stainless Steel
Mounting Plate
Gasket
Louvered Cover
Plate
Stainless Steel
Flow Tube
Mounting Plate
Gasket
Thin Silicone Caulking
(apply around tube and between
stainless steel plate and wall to seal
unit penetration)
Terminal
For connection of
transmitter to FMS-1655.
Flow Tube
When Flow Tube mounting plate
is located directly opposite the
sensor, flow tubing must be cut as
short as possible to prevent kinks.
To FMS-1655 Controller
Wall Section
(cutaway view)
Orange wall bracket
to be installed first
by using the rotating
clamps for secure
wall attachment.
MOUNTING/WIRING
Triatek reserves the right to change product specifications without notice.