CHAPTER 2 - COMBUSTION AIR & VENTING
7. Any improper operation of the common venting sys-
tem should be corrected so the installation conforms
with the National Fuel Gas Code (NFPA 54 / ANSI
Z223.1) for installations in the U.S. or CAN/CSA B149.1
for installations in Canada. When resizing any por-
tion of the common venting system, the common
venting system should be resized to approach the
minimum size as determined using the appropriate
tables in Chapter 13 of the National Fuel Gas Code
(NFPA 54 / ANSI Z223.1) for installations in the U.S. or
CAN/CSA B149.1 for installations in Canada.
Do not install the INSTINCT into a common vent
with any other gas or oil appliances. This will
cause flue gas spillage or appliance malfunction,
resulting in substantial property damage, serious
injury, or death.
2.7. Carbon Monoxide Detector Installation
Triangle Tube follows the recommended advice of CPSC
and requires the installation of a minimum of two (2)
carbon monoxide detectors with an alarm and battery
back-up if hard wired; one in the mechanical room
where the boiler is located and another installed in the
area outside each sleeping area for all installations.
Each carbon monoxide detector shall comply with
NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
Consult the local authority having jurisdiction for any
additional carbon monoxide detector requirements
in your area. See
Section 2.8 on page 10
for
additional carbon monoxide detector requirements in
Massachusetts.
A byproduct of any gas fired appliance is carbon
monoxide. Failure to install carbon monoxide
detectors with alarms can result in serious injury,
or death.
DANGER
WARNING
2.8. Commonwealth of Massachusetts
Installation Requirements
For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used
in whole or in part for residential purposes, including
those owned or operated by the Commonwealth and
where the side wall exhaust vent termination is less
than seven (7) feet above finished grade in the area
of the venting, including but not limited to decks and
porches, the following requirements shall be satisfied:
2.8.1 Installation of Carbon Monoxide Detectors.
1. At the time of installation of the side wall horizontal
vented gas fueled equipment, the installing plumber
or gasfitter shall observe that a hard wired carbon
monoxide detector with an alarm and battery back-up
is installed on the floor level where the gas equipment
is to be installed.
2. In addition, the installing plumber or gasfitter shall
observe that a battery operated or hard wired carbon
monoxide detector with an alarm is installed on each
additional level of the dwelling, building or structure
served by the side wall horizontal vented gas fueled
equipment.
3. It shall be the responsibility of the property owner to
secure the services of qualified licensed professionals for
the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally
vented gas fueled equipment is installed in a
crawl space or an attic, the hard wired carbon
monoxide detector with alarm and battery
back-up may be installed on the next adjacent
floor level.
b. In the event that the requirements of this
subdivision can not be met at the time of
completion of installation, the owner shall have
a period of thirty (30) days to comply with the
above requirements; provided, however, that
during said thirty (30) day period, a battery
operated carbon monoxide detector with an
alarm shall be installed.
Содержание Instinct COMBI 155
Страница 2: ...INTENTIONALLY LEFT BLANK...
Страница 16: ...INTENTIONALLY LEFT BLANK...
Страница 24: ...INTENTIONALLY LEFT BLANK...
Страница 46: ...INTENTIONALLY LEFT BLANK...
Страница 54: ...INTENTIONALLY LEFT BLANK...
Страница 76: ...INTENTIONALLY LEFT BLANK...
Страница 86: ...INTENTIONALLY LEFT BLANK...
Страница 90: ...INTENTIONALLY LEFT BLANK...
Страница 92: ...INTENTIONALLY LEFT BLANK...
Страница 94: ...INTENTIONALLY LEFT BLANK...
Страница 122: ......
Страница 123: ......
Страница 124: ......
Страница 125: ......
Страница 126: ......
Страница 127: ......