Bacteria can develop in the domestic water
system if certain minimum water temperatures
are not maintained. Failure to maintain at least
140°F [60°C] domestic hot water temperature
or use the Antilegionella function can result in
bacteria development, which can result in serious
injury, or death.
• Should overheating occur or if the gas supply fails
to shut off, turn OFF the manual gas control valve
external to the appliance.
•
Do not add cold make up water when the
appliance is hot. Thermal shock can potentially
cause cracks in the heat exchanger.
• Failure to comply with these instructions can
result in substantial property damage, serious
injury, or death.
Protection must be taken against excessive pressure!
TO PROTECT AGAINST EXCESSIVE PRESSURE:
•
Verify that a field supplied 150 psi pressure relief
valve is installed in the recommended location
for Combi models using the domestic hot water
function (DHW Side).
•
Verify the 30 psi relief valve supplied is installed
in the location provided (CH Side). In installations
where the CH pressure exceeds 30 psi, a 50 psi
relief valve (not included) can be installed in lieu of
the 30 psi relief valve.
•
To avoid injury, install the relief valves in
compliance with local code requirements.
Failure to comply with these instructions can
result in substantial property damage, serious
injury, or death.
• It is prohibited to carry out any modifications to the appliance
without prior written consent from Triangle Tube.
• Faulty parts must only be replaced by genuine Triangle
Tube factory parts.
• Failure to comply with these instructions can result in minor
property damage, or injury.
WARNING
WARNING
CAUTION
HOT WATER CAN SCALD!
Water temperature over 125ºF can cause severe
burns instantly or death from scalds.
•
Children, disabled and elderly are at highest
risk of being scalded.
Ū Never leave them unattended in or near
shower, bathtub or sink.
Ū Never allow small children to use a hot wa-
ter faucet or draw their own bath.
•
To avoid any potential scald hazard or if codes
require specific water temperatures at the hot
water faucet, the installer must:
Ū Install a thermostatic mixing valve at
this appliance and ensure it is working
property AND
Ū Set the domestic hot water temperature
to the lowest temperature which satisfies
your hot water needs.
Ū Feel and adjust water temperature before
bathing or showering.
Ū Water drained from the system drain
valves may be extremely hot.
TO AVOID INJURY:
•
Make sure all connections are tight.
•
Direct water flow away from any person.
•
Failure to comply with these instructions will
result in substantial property damage, serious
injury, or death
.
To prevent bacteria in the water system the
stored water temperature must be at least
140F. To prevent scalding it is mandatory to fit
a thermostatic valve in the domestic hot water
circuit.
DANGER
WARNING
xii
SAFE
TY
PRODUCT AND SAFETY INFORMATION
Содержание Instinct COMBI 155
Страница 2: ...INTENTIONALLY LEFT BLANK...
Страница 16: ...INTENTIONALLY LEFT BLANK...
Страница 24: ...INTENTIONALLY LEFT BLANK...
Страница 46: ...INTENTIONALLY LEFT BLANK...
Страница 54: ...INTENTIONALLY LEFT BLANK...
Страница 76: ...INTENTIONALLY LEFT BLANK...
Страница 86: ...INTENTIONALLY LEFT BLANK...
Страница 90: ...INTENTIONALLY LEFT BLANK...
Страница 92: ...INTENTIONALLY LEFT BLANK...
Страница 94: ...INTENTIONALLY LEFT BLANK...
Страница 122: ......
Страница 123: ......
Страница 124: ......
Страница 125: ......
Страница 126: ......
Страница 127: ......