3
CHAPTER
1
CHAPTER 1 - PRE-INSTALLATION REQUIREMENTS
1.4. Boiler Replacement
If the INSTINCT is replacing an existing boiler, the
following items should be checked and corrected prior
to installation:
• Boiler piping leaks and corrosion.
• Proper location and sizing of the expansion
tank on the boiler heating loop.
• The existing vent system is appropriate for the
INSTINCT and it is correctly installed. Refer to
the INSTINCT Vent Supplement for the vent
system requirements.
• Amount and quality of propylene glycol within
the system, if applicable.
1.5. Recommended Clearances
The INSTINCT is approved for zero clearance to com-
bustibles, excluding vent and boiler piping.
• Boiler piping must be a minimum 1/4 inch from
combustible materials.
• Reference the INSTINCT Vent Supplement for
vent pipe clearance requirements.
•
It is recommended that the following clearances
be maintained for serviceability:
• Top boiler jacket - 24 inches [610 mm].
• Front - 24 inches [610 mm].
• Bottom boiler piping - 0 inches
• Rear - 0 inches
• Sides - 6" (153mm) from side of appliance
and 6" from side of hydraulic separator.
•
When maintaining less than recommended
service clearances, some product labeling,
including the rating label, may become hidden
and unreadable.
BEST PRACTICE
BEST PRACTICE
NOTICE
If the recommended clearances listed above
cannot be maintained or the enclosure in
which the boiler is installed is less than 70
cubic feet, the space must be ventilated.
See Section 2.2 on page 6.
• When installing the INSTINCT in a confined
space, sufficient air must be provided to
allow, under normal operating conditions,
proper air flow around the product to
maintain ambient temperatures within
safe limits to comply with the National Fuel
Gas Code (NFPA 54 / ANSI Z223.1)
• Failure to comply with these instructions
can result in substantial property
damage, serious injury, or death.
1.6. Residential Garage Installations
When installing the INSTINCT in a residential garage,
the following special precautions per NFPA 54/ANSI
Z223.1 must be taken:
• When installing the floor standing Instinct in a
garage precautions in accordance with NFPA 54/
ANSI Z223.1 are met by the construction of the
appliance. The incoming air for combustion, the
burner and the ignition device are all situated
more than 18 inches(458mm) above the floor.
The height of these components is 29 inches
(755mm) above the garage floor.
• Locate or protect the unit in a manner so it
cannot be damaged by a moving vehicle.
WARNING
Содержание Instinct COMBI 155
Страница 2: ...INTENTIONALLY LEFT BLANK...
Страница 16: ...INTENTIONALLY LEFT BLANK...
Страница 24: ...INTENTIONALLY LEFT BLANK...
Страница 46: ...INTENTIONALLY LEFT BLANK...
Страница 54: ...INTENTIONALLY LEFT BLANK...
Страница 76: ...INTENTIONALLY LEFT BLANK...
Страница 86: ...INTENTIONALLY LEFT BLANK...
Страница 90: ...INTENTIONALLY LEFT BLANK...
Страница 92: ...INTENTIONALLY LEFT BLANK...
Страница 94: ...INTENTIONALLY LEFT BLANK...
Страница 122: ......
Страница 123: ......
Страница 124: ......
Страница 125: ......
Страница 126: ......
Страница 127: ......