Space Temperature Averaging
Space temperature averaging is accomplished by wiring a number of remote sensors in a series/
parallel circuit.
Using the BAYSENS016* or BAYSENS017*, at least four sensors are required to accomplish space
temperature averaging.
Example #1 illustrates two series circuits with two sensors in each circiut wired in parallel. The
square of any number of remote sensors required.
Example #2 illustrates three sensors squared in a series/parallel circuit. Using BAYSENS032*, two
sensors are required to accomplish space temperature averaging. Example #3 illustrates the circuit
required for this senor.
Table 5
lists the temperature versus resistance coefficient for all sensing.
Table 5.
Temperature vs. resistance
Degrees F° Degrees C°
Nominal Resistance
-20°
-28.9°
170.1 K - Ohms
-15°
-26.1°
143.5 K - Ohms
-10°
-23.3°
121.4 K - Ohms
-5°
-20.6°
103.0 K - Ohms
0°
-17.8°
87.56 K - Ohms
5°
-15.0°
74.65 K - Ohms
10°
-12.2°
63.80 K - Ohms
15°
-9.4°
54.66 K - Ohms
20°
-6.7°
46.94 K - Ohms
25°
-3.8°
40.40 K - Ohms
30°
-1.1°
34.85 K - Ohms
35°
1.7°
30.18 K - Ohms
40°
4.4°
26.22 K - Ohms
45°
7.2°
22.85 K - Ohms
50°
10.0°
19.96 K - Ohms
55°
12.8°
17.47 K - Ohms
60°
15.6°
15.33 K - Ohms
65°
18.3°
13.49 K - Ohms
70°
21.1°
11.89 K - Ohms
75°
23.9°
10.50 K - Ohms
80°
26.7°
9.297 K - Ohms
85°
29.4°
8.247 K - Ohms
90°
32.2°
7.330 K - Ohms
95°
35.0°
6.528 K - Ohms
100°
37.8°
5.824 K - Ohms