Table 33.
General unit warning (continued)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Service Required.
Affects the alarm for Dirty
Strainer, preventing alarm
from working properly.
The Pressure sensor is
reading either above is
maximum value or below
is minimum value,
resulting in a Fault
Condition after 3 point
updates.
•
Sensor is not wired
properly: Verify
sensor wiring to the
XM Module.
•
XM Module is not
communicating.
Ensure that the XM
Module is up and
talking to the UC600.
•
Sensor has failed.
Verify if sensor has
any resistance on it,
should be 8-12k of
resistance on the
thermistor.
None, alarm clears once
sensor is in a normal
state.
Condenser Tee Strainer Low Pressure (In Fault)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Service Required.
Affects the alarm for Dirty
Strainer, preventing alarm
from working properly.
The Pressure sensor is
reading either above is
maximum value or below
is minimum value,
resulting in a Fault
Condition after 3 point
updates.
•
Sensor is not wired
properly: Verify
sensor wiring to the
XM Module.
•
XM Module is not
communicating.
Ensure that the XM
Module is up and
talking to the UC600.
•
Sensor has failed.
Verify if sensor has
any resistance on it,
should be 8-12k of
resistance on the
thermistor.
None, alarm clears once
sensor is in a normal
state.
Condenser Water Flow Switch (In Fault)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Service Required.
Output may not function
properly.
The UC600 Controller has
lost communications with
the Output.
•
XM Module is not
communicating.
Ensure that the XM
Module is up and
talking to the UC600.
•
Output has gone bad
on XM Module.
None, alarm clears once
sensor is in a normal
state.
Unit Alarm Output Command (In Fault)