Table 19.
Electrical service sizing data — motors — 40 to 80 tons
Tonnage
Model
Number
Unit Wiring
Motor Data
Compressor (EA)
Fan (EA)
Fixed Speed
Variable Speed
VSD
Nameplate
Voltage
Voltage
Range
MCA MOP Disc Qty
RLA
LRA Qty
Max
Input (A)
Qty
kW
FLA
40
SCWMN04LF
208-230/60/3
187 - 253
186.6
250
200
1
55.77
340
1
56
3
6.15 18.6
SCWMN040F
208-230/60/3
187-253
221.6
300
225
1
55.77
340
1
84
3
6.15 18.6
SCWMN04L4
460/60/3
414 - 506
90.7
125
100
1
23.72
110
1
30
3
6.15
9
SCWMN0404
460/60/3
414-506
128.2
200
125
1
23.72
110
1
60
3
6.15
9
50
SCWMN05LF
208-230/60/3
187 - 253
233.4
300
250
2
51.28
300
1
56
3
6.15 18.6
SCWMN050F
208-230/60/3
187-253
268.4
350
300
2
51.28
300
1
84
3
6.15 18.6
SCWMN05L4
460/60/3
414 - 506
113.2
150
125
2
23.1
150
1
30
3
6.15
9
SCWMN0504
460/60/3
414-506
150.7
200
150
2
23.1
150
1
60
3
6.15
9
60
SCWMN06LF
208-230/60/3
187 - 253
260.9
300
300
2
55.77
340
1
56
4
6.15 18.6
SCWMN060F
208-230/60/3
187-253
295.9
375
300
2
55.77
340
1
84
4
6.15 18.6
SCWMN06L4
460/60/3
414 - 506
123.4
150
150
2
23.72
110
1
30
4
6.15
9
SCWMN0604
460/60/3
414-506
160.9
225
175
2
23.72
110
1
60
4
6.15
9
70
SCWMN07LF
208-230/60/3
187-253
321.8
375
350
3
51.28
300
1
56
5
6.15 18.6
SCWMN070F
208-230/60/3
187-253
356.9
450
375
3
51.28
300
1
84
5
6.15 18.6
SCWMN07L4
460/60/3
414-506
154.2
175
175
3
23.1
150
1
30
5
6.15
9
SCWMN0704
460/60/3
414-506
191.7
250
200
3
23.1
150
1
60
5
6.15
9
80
SCWMN08LF
208-230/60/3
187-253
335.3
400
375
3
55.77
340
1
56
5
6.15 18.6
SCWMN080F
208-230/60/3
187-253
370.3
450
400
3
55.77
340
1
84
5
6.15 18.6
SCWMN08L4
460/60/3
414-506
156.2
175
175
3
23.72
110
1
30
5
6.15
9
SCWMN0804
460/60/3
414-506
193.7
250
200
3
23.72
110
1
60
5
6.15
9
Notes:
1
.
MCA: Minimum Circuit Ampacity is 125% of the largest compressor RLA or Drive input current, plus 100% of the other compressor (s) RLA,
plus the sum of the condenser fan RLA, plus any other load rated at 1 AMP or more.
2
.
Maximum Breaker Overcurrent Protection (MOP): 225% of the largest compressor RLA or VSD drive Input, plus 100% of the other compressor
(s) RLA, plus the sum of the condenser fan Motor/Drive FLA, plus any other load rated at 1 AMP or more.
3
.
Recommended disconnect switch: 110% to 115% of the sum of the RLA of the compressors, VSD drive input, fan motor/drive and controls FLA.
4
.
RLA: Rated in accordance with UL standard 1995
5
.
Local codes may take precedence.
6
.
Fix speed compressor are across the line starting, the VSD compressors are controlled by VSD drive. Compressors will never start
simultaneously.
7
.
Voltage utilization range is ±10 percent.
Table 20.
Electrical data — 40 to 80 tons
Tonnage
Model Number
Nameplate Voltage
Compressor (EA)
Fan (EA)
Fixed Speed
Variable Speed
VSD
Qty
RLA
LRA Qty Max Input (A) Qty
kW
FLA
40
SCWMN04LF
208-230/60/3
1
55.77
340
1
56
3
0.5
18.6
SCWMN040F
208-230/60/3
1
55.77
340
1
84
3
6.15 18.6
SCWMN04L4
460/60/3
1
23.72
110
1
30
3
0.5
9
SCWMN0404
460/60/3
1
23.72
110
1
60
3
6.15
9
50
SCWMN05LF
208-230/60/3
2
51.28
300
1
56
3
0.5
18.6
SCWMN050F
208-230/60/3
2
51.28
300
1
84
3
6.15 18.6
SCWMN05L4
460/60/3
2
23.1
150
1
30
3
0.5
9
SCWMN0504
460/60/3
2
23.1
150
1
60
3
6.15
9