PKG-SVX027C-EN
45
Table 22.
Fan motor electrical data — 40 to 80 tons
Tonnage
Model Number
Nameplate Voltage
Fan (EA) - VSD
Qty
kW
FLA
40
SCWMN04LF
208-230/60/3
3
6.15
18.6
SCWMN040F
208-230/60/3
3
6.15
18.6
SCWMN04L4
460/60/3
3
6.15
9
SCWMN0404
460/60/3
3
6.15
9
50
SCWMN05LF
208-230/60/3
3
6.15
18.6
SCWMN050F
208-230/60/3
3
6.15
18.6
SCWMN05L4
460/60/3
3
6.15
9
SCWMN0504
460/60/3
3
6.15
9
60
SCWMN06LF
208-230/60/3
4
6.15
18.6
SCWMN060F
208-230/60/3
4
6.15
18.6
SCWMN06L4
460/60/3
4
6.15
9
SCWMN0604
460/60/3
4
6.15
9
70
SCWMN07LF
208-230/60/3
5
6.15
18.6
SCWMN070F
208-230/60/3
5
6.15
18.6
SCWMN07L4
460/60/3
5
6.15
9
SCWMN0704
460/60/3
5
6.15
9
80
SCWMN08LF
208-230/60/3
5
6.15
18.6
SCWMN080F
208-230/60/3
5
6.15
18.6
SCWMN08L4
460/60/3
5
6.15
9
SCWMN0804
460/60/3
5
6.15
9
Static Pressure Sensor
Installation (VAV units only)
Supply air static pressure controls the inverter option.
A bulkhead fitting and a roll of vinyl tubing is provided
for direct insertion into ductwork. If a specific head
assembly or remote location is desired, then this
material will be the responsibility of the installer. There
are two pressure transducers mounted on the side of
the control panel. The top is the static pressure
transducer and the bottom is the filter differential
transducer.
Sensor Location
1. Install static pressure sensor in specified location or
section of ductwork most critical to the VAV
operation.
2. If installation location is remote to transducer in
control panel, do not exceed 250 feet for ¼-inch OD
tubing or 500 feet for 3/8-inch OD tubing.
Installing the Tubing Sensor
1. Unscrew the ¼-inch bulkhead fitting provided.
2. Drill ½-inch hole in ductwork at desired location.
3. Insert male end of bulkhead fitting through the hole
from inside the duct.
4. Insert ¼-inch tubing through both halves of union
bulkhead fitting into ductwork.
5. Screw female end and tighten onto ductwork.
6. Run the opposite end of tubing through hole in the
top of the control panel cabinet.
7. Connect to the push-on connection at the top
pressure transducer in the control panel.