PKG-SVX027C-EN
55
Table 24.
Points list
Hardware Connection
Point Name
Point Setup
UC600
PI
Supply Duct Static Pressure Sensor
Honeywell Pressure Sensor
BO1
—
—
BO2
—
—
BO3
—
—
BO4
—
—
AO1/UI9
Water Side Economizer
2 Vdc = 0%, 10 Vdc = 100%
AO2/UI10
High Duct Temp Cutout (Optional)
Open = Tripped, Closed = Normal
AO3/UI11
Compressor 1 Speed Command
1.7 Vdc = Min Speed, 10 Vdc = Max Speed
AO4/UI12
Compressor 1 High Pressure Cutout
Open = Alarm, Closed = Normal
AO5/UI13
Compressor 2 High Pressure Cutout
Open = Alarm, Closed = Normal
AO6/UI14
Compressor 2 Safety Circuit Stauts
Open = Circuit Open, Closed = Circuit Complete
UI1
Compressor 3 High Pressure Cutout
Open = Alarm, Closed = Normal
UI2
Compressor 3 Safety Circuit Status
Open = Circuit Open, Closed = Circuit Complete
UI3
Discharge Air Temperature Local
10K Ohm Resistor Trane Type 2
UI4
Entering Air Temperature Local
10K Ohm Resistor Trane Type 2
UI5
ESTOP
Open = Normal, Closed = Emergency Stop
UI6
Exterior Auto/Stop
Open = Auto, Closed = Exterior Stop
UI7
Compressor 1 Status
Open = Off, Closed = Runing
UI8
Occupancy Input
Open = Unoccupied, Closed = Occupied
XM70.1
PI
Air Filter Differential Pressure
Honeywell Pressure Sensor
BO1
Heat Output 1
Open = Off, Closed = On
BO2
Heat Output 2
Open = Off, Closed = On
BO3
Heat Output 3
Open = Off, Closed = On
BO4
—
—
AO1/UI9
Supply Fan 1 Speed Command
0 Vdc = 0%, 10 Vdc = 100%
AO2/UI10
Supply Fan 2 Speed Command
0 Vdc = 0%, 10 Vdc = 100%
AO3/UI11
Supply Fan 3 Speed Command
0 Vdc = 0%, 10 Vdc = 100%
AO4/UI12
Supply Fan 4 Speed Command
0 Vdc = 0%, 10 Vdc = 100%
AO5/UI13
Morning Warmup Input
Open = Off, Closed = Morning Warmup
AO6/UI14
Heating Output 1 Command
2 Vdc = 100% Open, 10 Vdc = 0% Open
UI1
Supply Fan 1 VFD Fault
Open = Normal, Closed = Fault
UI2
Supply Fan 2 VFD Fault
Open = Normal, Closed = Fault
UI3
Supply Fan 3 VFD Fault
Open = Normal, Closed = Fault
UI4
Supply Fan 4 VFD Fault
Open = Normal, Closed = Fault
UI5
Space Temperature Local
10K Ohm Resistor Trane Type 2
UI6
—
—
UI7
Compressor 1 VFD Fault
Open = Normal, Closed = Alarm
UI8
Condenser Water Flow Switch
Open = No Flow, Closed = Flow
XM32.2
BO1
Supply Fan 1 Start Stop Command
NO Open = Stop, NO Closed = Run; NC not used
BO2
Supply Fan 2 Start Stop Command
NO Open = Stop, NO Closed = Run; NC not used
BO3
Supply Fan 3 Start Stop Command
NO Open = Stop, NO Closed = Run; NC not used
BO4
Supply Fan 4 Start Stop Command
NO Open = Stop, NO Closed = Run; NC not used