PKG-SVX027C-EN
81
Table 29.
Compressor alarming (continued)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Critical Alarm.
Compressor will be locked
out and prevented from
running until this
diagnostic is cleared.
The Calculated superheat
is above 25 degrees for 10
minutes.
•
Low Charge on unit.
•
Malfunctioning TXV.
•
Too high of a heat
load.
•
Too much air across
the evaporator.
Manual Reset required
once the issue is resolved.
User must toggle the
Compressor (1-4) Failure
Reset.
Diagnostic: Compressor (1-4) Low Superheat (In Alarm)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Critical Alarm.
Compressor will be locked
out and prevented from
running until this
diagnostic is cleared.
The Calculated superheat
is below 4 degrees for 5
minutes.
•
Over Charge on unit.
•
Malfunctioning TXV.
•
Dirty Condenser
tubes.
•
TXV Bulb is not
strapped tightly to
suction line.
•
Too little air across
the evaporator.
Manual Reset required
once the issue is resolved.
User must toggle the
Compressor (1-4) Failure
Reset.
Diagnostic: Compressor 1 Safety Circuit Alarm (In Alarm)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Critical Alarm.
Compressor will be locked
out and prevented from
running until this
diagnostic is cleared.
The Compressor VFD has
indicated that it’s in fault
or the Compressor is
commanded on but does
not indicate status.
•
VFD has an issue.
•
Relay starting
compressor is
malfunctioning.
•
XM Module
commanding
compressor relay is
failed or not
communicating.
Manual Reset required
once the issue is resolved.
User must toggle the
Compressor 1 Failure
Reset.
Diagnostic: Compressor (2-4) Safety Circuit Alarm (In Alarm)
Notification Class
Action
Reason
Typical Causes
Reset Required