Controls Interface
Operational Features
Entering Evaporator Water Temperature
When one or both compressors are running, the UCM continually monitors
and compares the entering and leaving evaporator water temperatures. If the
temperature of the entering water drops more than 2 F below the leaving
water temperature for more than 100 degree F seconds, the UCM uses this
to indicate a loss of water flow through the evaporator. This will shut down
that circuit's compressor and will display an MMR diagnostic.
Current Limit Setpoint
The current limit setpoint for the system (front panel or remote) are entered
through the Clear Language Display menus. The current limit setpoint for
each compressor is shown in Table 16.
Based upon current levels received at the UCM, the compressor slide valve is
modulated to prevent the actual chiller current from exceeding the CLS.
When a compressor is turned off, the CLS for the remaining running
compressor shall be reset upward immediately. When a compressor is
added, the CLS for the running compressor shall be ramped downward at a
rate not less than 10% RLA per minute to the new setpoint.
Low Ambient Lockout
The lockout provides a method for preventing unit start-up when the outdoor
air temperature is below the setpoint. If the outdoor temperature goes below
the setpoint during operation, the UCM will go through a normal shutdown of
the unit. If the outdoor temperature subsequently increases to 5 F above the
setpoint, the UCM will automatically re-enable the unit. The low ambient
lockout feature has a range from -20 F to 60 F
Electronic Expansion Valve (EXV) Test
This test can be performed only when the Stop key has been pressed. It will
confirm proper operation of the electronic expansion valve and the EXV
module.
Once the test has been initiated at the Clear Language Display, the UCM will:
1.
Overdrive the EXV closed (25 seconds).
2.
Overdrive the EXV open (25 seconds).
3.
Overdrive the EXV closed (25 seconds).
4.
Reset the display to disable and end the test.
The EXV produces an audible clicking sound when it is driven against its end
stops. Step 1 drives the EXV to its closed position, during which time service
personnel can move from the Clear Language Display to the EXV.
NOTE:
A tool may be needed to aid in hearing the clicking of the EXV, such
as a screwdriver held between the EXV and the ear.
When Step 1 completes, the clicking stops and the UCM begins to open the
EXV. When the EXV is fully opened, the valve will begin to click against its end
stop. The service personnel must be prepared to time the period between
the end of clicking in Step 1 and the beginning of clicking in Step 2.
The time between the end of clicking in Step 2 and the beginning of clicking
in Step 3 must also be recorded. The time for the EXV to go from fully closed
to fully open (which is the first time recorded) should be approximately 15
seconds. The time to go back to fully closed (which is the second time
recorded) is approximately 15 seconds.
Содержание RTAA-100
Страница 12: ...12 RTAA SVX01A EN Installation Mechanical Figure 4 RTAA Rigging and Lifting Weights Packaged Unit...
Страница 13: ...RTAA SVX01A EN 13 Installation Mechanical Figure 5 RTAA Rigging and Lifting Weights Remote Evaporator...
Страница 14: ...14 RTAA SVX01A EN Installation Mechanical Figure 6 RTAA Rigging and Lifting Weights Pump Package Aluminum Fins...
Страница 15: ...RTAA SVX01A EN 15 Installation Mechanical Figure 7 RTAA Rigging and Lifting Weights Pump Package Copper Fins...
Страница 18: ...18 RTAA SVX01A EN Installation Mechanical Figure 8 Dimensions and Clearances for RTAA Packaged Unit 70 125 Tons...
Страница 20: ...20 RTAA SVX01A EN Installation Mechanical Figure 10 Remote Evaporator Dimensions RTAA 70 125 Tons...
Страница 21: ...RTAA SVX01A EN 21 Installation Mechanical Figure 11 Remote Evaporator Dimensions RTAA 110 125 Tons...
Страница 25: ...RTAA SVX01A EN 25 Installation Mechanical Figure 14 Isolator Placement for RTAA with Remote Evaporator...
Страница 45: ...RTAA SVX01A EN 45 Installation Remote Evaporator Figure 24 Refrigerant Sensor Mounting and Wiring...
Страница 65: ...RTAA SVX01A EN 65 Installation Electrical Figure 31 Remote Display Panel Interconnecting Wiring...
Страница 110: ...110 RTAA SVX01A EN Start Up Procedures Figure 37 Unit Sequence of Operation...
Страница 143: ...RTAA SVX01A EN 143 Pump Package Figure 47 Pump Package Piping Schematic...
Страница 144: ...144 RTAA SVX01A EN Pump Package...
Страница 146: ...146 RTAA SVX01A EN 3327...
Страница 147: ...RTAA SVX01A EN 147...
Страница 148: ...148 RTAA SVX01A EN 3328...
Страница 149: ...RTAA SVX01A EN 149...
Страница 150: ...150 RTAA SVX01A EN 6516...
Страница 151: ...RTAA SVX01A EN 151...
Страница 152: ...152 RTAA SVX01A EN 3329...
Страница 153: ...RTAA SVX01A EN 153...
Страница 154: ...154 RTAA SVX01A EN 6472...
Страница 155: ...RTAA SVX01A EN 155...
Страница 156: ...RTAA SVX01A EN 156 3330...
Страница 157: ...157 RTAA SVX01A EN...
Страница 158: ...158 RTAA SVX01A EN 6046...
Страница 159: ...RTAA SVX01A EN 159...
Страница 160: ...160 RTAA SVX01A EN 3331...
Страница 161: ...RTAA SVX01A EN 161...
Страница 162: ...162 RTAA SVX01A EN 6519...
Страница 163: ...RTAA SVX01A EN 163...
Страница 164: ...164 RTAA SVX01A EN 6047...
Страница 165: ...RTAA SVX01A EN 165...
Страница 166: ...166 RTAA SVX01A EN 3325...
Страница 167: ...RTAA SVX01A EN 167...
Страница 168: ...168 RTAA SVX01A EN 6048...
Страница 169: ...RTAA SVX01A EN 169...
Страница 172: ...172 RTAA SVX01A EN 3326...
Страница 173: ...RTAA SVX01A EN 173...
Страница 174: ...174 RTAA SVX01A EN 6049...
Страница 175: ...RTAA SVX01A EN 175...
Страница 176: ...176 RTAA SVX01A EN 6463...
Страница 177: ......