46
RTAA-SVX01A-EN
Installation — Remote Evaporator
Leak Test and Evacuation
After installation of the refrigerant piping, thoroughly test the system for
leaks. Pressure test the system at pressures required by local codes.
Immediately before evacuation, install the liquid line filter cores. These will be
shipped with the evaporator.
NOTE:
Do not install these before the circuit is ready for evacuation, as the
cores will absorb moisture from the atmosphere.
For field evacuation, use a rotary-type vacuum pump capable of pulling a
vacuum of 100 microns or less. Follow the pump manufacturer's instructions
for proper use of the pump. The line used to connect the pump to the system
should be copper and be the largest diameter that can be practically used. A
larger line size with minimum flow resistance can significantly reduce
evacuation time.
Use the ports on the compressor suction service valves and the liquid line
shutoff valves for access to the system for evacuation. Insure that the
compressor suction service valve, the liquid line shutoff valve, the oil line
shutoff valve and any field installed valves are open in the proper position
before evacuating.
Insulate the entire suction line and the suction accumulator line. Where the
line is exposed to the weather, wrap it with weatherproof tape and seal with
weather-proof compound.
Refrigerant and Additional Oil Charge
Refrigerant Charge Determination
The approximate amount of refrigerant charge required by the system must
be determined by referring to
Table 8
and must be verified by running the
system and checking the liquid line sightglasses.
To determine the appropriate charge, first refer to
Table 8
to establish the
required charge without the field-installed piping. Next, determine the charge
required for the field-installed piping by referring to
Table 9
.
NOTE:
The amounts of refrigerant listed in
Table 9
are based on 100 feet of
pipe. Actual requirements will be in direct proportion to the actual length of
piping.
NOTE:
Table 9
assumes:
The approximate amount of refrigerant is therefore the sum of the values
determined from
Table 8
and
Table 9
.
Table 8
System Refrigerant Charge
Circuit Size
Lbs. of R- 22
35
58
40
61
50
73
60
98
Liquid Temperature =
100 F
Suction Temperature =
35 F
Suction Superheat Temperature =
4 F
Содержание RTAA-100
Страница 12: ...12 RTAA SVX01A EN Installation Mechanical Figure 4 RTAA Rigging and Lifting Weights Packaged Unit...
Страница 13: ...RTAA SVX01A EN 13 Installation Mechanical Figure 5 RTAA Rigging and Lifting Weights Remote Evaporator...
Страница 14: ...14 RTAA SVX01A EN Installation Mechanical Figure 6 RTAA Rigging and Lifting Weights Pump Package Aluminum Fins...
Страница 15: ...RTAA SVX01A EN 15 Installation Mechanical Figure 7 RTAA Rigging and Lifting Weights Pump Package Copper Fins...
Страница 18: ...18 RTAA SVX01A EN Installation Mechanical Figure 8 Dimensions and Clearances for RTAA Packaged Unit 70 125 Tons...
Страница 20: ...20 RTAA SVX01A EN Installation Mechanical Figure 10 Remote Evaporator Dimensions RTAA 70 125 Tons...
Страница 21: ...RTAA SVX01A EN 21 Installation Mechanical Figure 11 Remote Evaporator Dimensions RTAA 110 125 Tons...
Страница 25: ...RTAA SVX01A EN 25 Installation Mechanical Figure 14 Isolator Placement for RTAA with Remote Evaporator...
Страница 45: ...RTAA SVX01A EN 45 Installation Remote Evaporator Figure 24 Refrigerant Sensor Mounting and Wiring...
Страница 65: ...RTAA SVX01A EN 65 Installation Electrical Figure 31 Remote Display Panel Interconnecting Wiring...
Страница 110: ...110 RTAA SVX01A EN Start Up Procedures Figure 37 Unit Sequence of Operation...
Страница 143: ...RTAA SVX01A EN 143 Pump Package Figure 47 Pump Package Piping Schematic...
Страница 144: ...144 RTAA SVX01A EN Pump Package...
Страница 146: ...146 RTAA SVX01A EN 3327...
Страница 147: ...RTAA SVX01A EN 147...
Страница 148: ...148 RTAA SVX01A EN 3328...
Страница 149: ...RTAA SVX01A EN 149...
Страница 150: ...150 RTAA SVX01A EN 6516...
Страница 151: ...RTAA SVX01A EN 151...
Страница 152: ...152 RTAA SVX01A EN 3329...
Страница 153: ...RTAA SVX01A EN 153...
Страница 154: ...154 RTAA SVX01A EN 6472...
Страница 155: ...RTAA SVX01A EN 155...
Страница 156: ...RTAA SVX01A EN 156 3330...
Страница 157: ...157 RTAA SVX01A EN...
Страница 158: ...158 RTAA SVX01A EN 6046...
Страница 159: ...RTAA SVX01A EN 159...
Страница 160: ...160 RTAA SVX01A EN 3331...
Страница 161: ...RTAA SVX01A EN 161...
Страница 162: ...162 RTAA SVX01A EN 6519...
Страница 163: ...RTAA SVX01A EN 163...
Страница 164: ...164 RTAA SVX01A EN 6047...
Страница 165: ...RTAA SVX01A EN 165...
Страница 166: ...166 RTAA SVX01A EN 3325...
Страница 167: ...RTAA SVX01A EN 167...
Страница 168: ...168 RTAA SVX01A EN 6048...
Страница 169: ...RTAA SVX01A EN 169...
Страница 172: ...172 RTAA SVX01A EN 3326...
Страница 173: ...RTAA SVX01A EN 173...
Страница 174: ...174 RTAA SVX01A EN 6049...
Страница 175: ...RTAA SVX01A EN 175...
Страница 176: ...176 RTAA SVX01A EN 6463...
Страница 177: ......