RTAA-SVX01A-EN
131
Diagnostics
Oil System Fault - Ckt 1
CMR
Entering Oil Temp on either compressor of the given circuit
reads a temperature x degrees below the given ckts' saturated
condenser temperature for more than 30 minutes where x is
the Oil Loss Differential Setpoint (2 degree F hysterisis to
clear timer).
Oil System Fault - Ckt 2
CMR
Same as for Ckt 1, above.
Outdoor Air Temp Sensor (Both Outdoor Air
Reset and Low Ambient Lockout not selected)
None
Open or short.
a.
Display dashes e.g. “14----”.
Outdoor Air Temp Sensor (Either Outdoor Air
Reset or Low Ambient Lockout selected.)
I FW
Open or short.
a.
Use end of range value (whatever value the open or
short.
b.
Clear diag. when the resistance returns to normal range.
Over Voltage
MAR
Line voltage above + 10% of nominal. (Must hold = + 10% of
nominal. Must trip = + 15% of nominal. Reset differential =
min. of 2% and max. of 4%. Time to trip = minimum of 10 sec.
and maximum of 20 seconds.)
Design: Nom. trip: 15 seconds at greater than 113.5%,
± 2.8% at 200V, or ± 1.8% at 575V, Auto reset at 110.5% or
less.
Overload Trip - CPRSR A
CMR
Cprsr current exceeded overload time vs. trip characteristic.
Overload Trip - CPRSR B
CMR
Same as Diagnostic for Cprsr A.
Overload Trip - CPRSR C
CMR
Same as Diagnostic for Cprsr A.
Overload Trip - CPRSR D
CMR
Same as Diagnostic for Cprsr A.
Phase Loss - Cprsr A
CMR
No current was sensed on one or more of the current x former
inputs. (Must hold = 20% RLA. Must trip = 5% RLA.) Time to
trip shall be 1 second minimum, 3 seconds maximum.
Phase Loss - Cprsr B
CMR
Same as Diagnostic for Cprsr A, above.
Phase Loss - Cprsr C
CMR
Same as Diagnostic for Cprsr A, above.
Phase Loss - Cprsr D
CMR
Same as Diagnostic for Cprsr A, above.
Phase Reversal - Cprsr A
CMR
A phase reversal was detected on the incoming current. On a
compressor startup the phase reversal logic must detect and
trip in a maximum of 1.0 second from compressor start.
Phase Reversal - Cprsr B
CMR
Same as Diagnostic for Cprsr A, above.
Phase Reversal - Cprsr C
CMR
Same as Diagnostic for Cprsr A, above.
Phase Reversal - Cprsr D
CMR
Same as Diagnostic for Cprsr A, above.
Phase Rev Prot Lost Cprsr A
CMR
The phase reversal protection on compressor A has become
inoperative. The phase rotation protection system failed to
detect 2 in a row of one of the four phase circuit states: Phase
reversal, Phase rotation OK, Phase A lost., Phase B lost.
Phase Rev Prot Lost - Cprsr B
CMR
Same as Cprsr A, above, but Cprsr B.
Phase Rev Prot Lost - Cprsr C
CMR
Same as Cprsr A, above, but Cprsr C.
Phase Rev Prot Lost - Cprsr D
CMR
Same as Cprsr A, above, but Cprsr D.
Phase Unbalance - Cprsr A
CMR
A 15% phase unbalance condition has been detected.
Phase Unbalance - Cprsr B
CMR
Same as Diagnostic for Cprsr A.
Phase Unbalance - Cprsr C
CMR
Same as Diagnostic for Cprsr A.
Table 19
Diagnostic Codes
Diagnostic Description
Type
Cause
Содержание RTAA-100
Страница 12: ...12 RTAA SVX01A EN Installation Mechanical Figure 4 RTAA Rigging and Lifting Weights Packaged Unit...
Страница 13: ...RTAA SVX01A EN 13 Installation Mechanical Figure 5 RTAA Rigging and Lifting Weights Remote Evaporator...
Страница 14: ...14 RTAA SVX01A EN Installation Mechanical Figure 6 RTAA Rigging and Lifting Weights Pump Package Aluminum Fins...
Страница 15: ...RTAA SVX01A EN 15 Installation Mechanical Figure 7 RTAA Rigging and Lifting Weights Pump Package Copper Fins...
Страница 18: ...18 RTAA SVX01A EN Installation Mechanical Figure 8 Dimensions and Clearances for RTAA Packaged Unit 70 125 Tons...
Страница 20: ...20 RTAA SVX01A EN Installation Mechanical Figure 10 Remote Evaporator Dimensions RTAA 70 125 Tons...
Страница 21: ...RTAA SVX01A EN 21 Installation Mechanical Figure 11 Remote Evaporator Dimensions RTAA 110 125 Tons...
Страница 25: ...RTAA SVX01A EN 25 Installation Mechanical Figure 14 Isolator Placement for RTAA with Remote Evaporator...
Страница 45: ...RTAA SVX01A EN 45 Installation Remote Evaporator Figure 24 Refrigerant Sensor Mounting and Wiring...
Страница 65: ...RTAA SVX01A EN 65 Installation Electrical Figure 31 Remote Display Panel Interconnecting Wiring...
Страница 110: ...110 RTAA SVX01A EN Start Up Procedures Figure 37 Unit Sequence of Operation...
Страница 143: ...RTAA SVX01A EN 143 Pump Package Figure 47 Pump Package Piping Schematic...
Страница 144: ...144 RTAA SVX01A EN Pump Package...
Страница 146: ...146 RTAA SVX01A EN 3327...
Страница 147: ...RTAA SVX01A EN 147...
Страница 148: ...148 RTAA SVX01A EN 3328...
Страница 149: ...RTAA SVX01A EN 149...
Страница 150: ...150 RTAA SVX01A EN 6516...
Страница 151: ...RTAA SVX01A EN 151...
Страница 152: ...152 RTAA SVX01A EN 3329...
Страница 153: ...RTAA SVX01A EN 153...
Страница 154: ...154 RTAA SVX01A EN 6472...
Страница 155: ...RTAA SVX01A EN 155...
Страница 156: ...RTAA SVX01A EN 156 3330...
Страница 157: ...157 RTAA SVX01A EN...
Страница 158: ...158 RTAA SVX01A EN 6046...
Страница 159: ...RTAA SVX01A EN 159...
Страница 160: ...160 RTAA SVX01A EN 3331...
Страница 161: ...RTAA SVX01A EN 161...
Страница 162: ...162 RTAA SVX01A EN 6519...
Страница 163: ...RTAA SVX01A EN 163...
Страница 164: ...164 RTAA SVX01A EN 6047...
Страница 165: ...RTAA SVX01A EN 165...
Страница 166: ...166 RTAA SVX01A EN 3325...
Страница 167: ...RTAA SVX01A EN 167...
Страница 168: ...168 RTAA SVX01A EN 6048...
Страница 169: ...RTAA SVX01A EN 169...
Страница 172: ...172 RTAA SVX01A EN 3326...
Страница 173: ...RTAA SVX01A EN 173...
Страница 174: ...174 RTAA SVX01A EN 6049...
Страница 175: ...RTAA SVX01A EN 175...
Страница 176: ...176 RTAA SVX01A EN 6463...
Страница 177: ......