70
RTAA-SVX01A-EN
Operating Principles
Compressor Bearing Oil Supply
Oil is injected into the bearing housings located at each end of both the male
and female rotors. Each bearing housing is vented to compressor suction, so
that oil leaving the bearings returns through the compressor rotors to the oil
separator.
Compressor Rotor Oil Supply
Oil flows through this circuit directly from the master oil valve, through the oil
filter to the top of the compressor rotor housing. There it is injected along the
top of the rotors to seal clearance spaces between the rotors and the
compressor housing and to lubricate the rotors.
Female Unloader Valve
The position of the female unloader valve determines compressor capacity.
Its position is dependent on whether the backside of the female unloader
valve is exposed to the compressor discharge or suction pressure. See
Figure 33
.
The female unloader valve solenoid receives a constant signal from the UCM,
based on system cooling requirements. To load the compressor, the female
unloader valve solenoid is energized and discharge pressure is passed
through the normally-closed port and into the cylinder. This pushes the female
unloader valve closed.
To unload the compressor, the female unloader valve solenoid is de-energized
and the discharge pressure is relieved to the suction of the compressor. The
female unloader valve retracts into the cylinder and the compressor is
unloaded.
Just prior to a normal compressor shut-down, the male unload valve solenoid
is energized and the slide valve moves to the fully-unloaded position, so the
unit always starts fully unloaded.
Oil Filter
Each compressor is equipped with a replaceable-element oil filter. The filter
removes any impurities that could foul the solenoid valve orifices and
compressor internal oil supply galleries. This also prevents excessive wear of
compressor rotor and bearing surfaces. Refer to the maintenance portion of
this manual for recommended filter element replacement intervals.
Condenser Fan Staging
The fans on the RTAA 70 -125 Ton units are staged by logic in the UCM. The
UCM takes several different pressures and temperatures into account, to
determine when fans should be added or subtracted. Input from the outside
air temperature sensor, the saturated condensing refrigerant temperature
sensor, and the saturated evaporator refrigerant temperature sensor are
monitored to determine fan staging.
The number of fans activated at startup is dependant upon the outdoor air
temperature.
Figure 34
shows fan activation at different temperatures.
During normal operation, the micro uses PID control to maintain a 70±5 psid
between the condensing pressure and the evaporator pressure. Through the
use of algorithm logic, a fan will be added if the pressure differential is greater
than 75 psid and the fan inverter is at maximum speed.
A “Low Differential Pressure” diagnostic will take the circuit off-line if the
pressure differential falls below 40 psid for more than two minutes.
A “High Differential Pressure” diagnostic will take the circuit off-line if the
pressure differential increases to 350 psid or greater. This diagnostic can also
be produced if the pressure differential increases to the range between 320
Содержание RTAA-100
Страница 12: ...12 RTAA SVX01A EN Installation Mechanical Figure 4 RTAA Rigging and Lifting Weights Packaged Unit...
Страница 13: ...RTAA SVX01A EN 13 Installation Mechanical Figure 5 RTAA Rigging and Lifting Weights Remote Evaporator...
Страница 14: ...14 RTAA SVX01A EN Installation Mechanical Figure 6 RTAA Rigging and Lifting Weights Pump Package Aluminum Fins...
Страница 15: ...RTAA SVX01A EN 15 Installation Mechanical Figure 7 RTAA Rigging and Lifting Weights Pump Package Copper Fins...
Страница 18: ...18 RTAA SVX01A EN Installation Mechanical Figure 8 Dimensions and Clearances for RTAA Packaged Unit 70 125 Tons...
Страница 20: ...20 RTAA SVX01A EN Installation Mechanical Figure 10 Remote Evaporator Dimensions RTAA 70 125 Tons...
Страница 21: ...RTAA SVX01A EN 21 Installation Mechanical Figure 11 Remote Evaporator Dimensions RTAA 110 125 Tons...
Страница 25: ...RTAA SVX01A EN 25 Installation Mechanical Figure 14 Isolator Placement for RTAA with Remote Evaporator...
Страница 45: ...RTAA SVX01A EN 45 Installation Remote Evaporator Figure 24 Refrigerant Sensor Mounting and Wiring...
Страница 65: ...RTAA SVX01A EN 65 Installation Electrical Figure 31 Remote Display Panel Interconnecting Wiring...
Страница 110: ...110 RTAA SVX01A EN Start Up Procedures Figure 37 Unit Sequence of Operation...
Страница 143: ...RTAA SVX01A EN 143 Pump Package Figure 47 Pump Package Piping Schematic...
Страница 144: ...144 RTAA SVX01A EN Pump Package...
Страница 146: ...146 RTAA SVX01A EN 3327...
Страница 147: ...RTAA SVX01A EN 147...
Страница 148: ...148 RTAA SVX01A EN 3328...
Страница 149: ...RTAA SVX01A EN 149...
Страница 150: ...150 RTAA SVX01A EN 6516...
Страница 151: ...RTAA SVX01A EN 151...
Страница 152: ...152 RTAA SVX01A EN 3329...
Страница 153: ...RTAA SVX01A EN 153...
Страница 154: ...154 RTAA SVX01A EN 6472...
Страница 155: ...RTAA SVX01A EN 155...
Страница 156: ...RTAA SVX01A EN 156 3330...
Страница 157: ...157 RTAA SVX01A EN...
Страница 158: ...158 RTAA SVX01A EN 6046...
Страница 159: ...RTAA SVX01A EN 159...
Страница 160: ...160 RTAA SVX01A EN 3331...
Страница 161: ...RTAA SVX01A EN 161...
Страница 162: ...162 RTAA SVX01A EN 6519...
Страница 163: ...RTAA SVX01A EN 163...
Страница 164: ...164 RTAA SVX01A EN 6047...
Страница 165: ...RTAA SVX01A EN 165...
Страница 166: ...166 RTAA SVX01A EN 3325...
Страница 167: ...RTAA SVX01A EN 167...
Страница 168: ...168 RTAA SVX01A EN 6048...
Страница 169: ...RTAA SVX01A EN 169...
Страница 172: ...172 RTAA SVX01A EN 3326...
Страница 173: ...RTAA SVX01A EN 173...
Страница 174: ...174 RTAA SVX01A EN 6049...
Страница 175: ...RTAA SVX01A EN 175...
Страница 176: ...176 RTAA SVX01A EN 6463...
Страница 177: ......