Installation — Electrical
Low Voltage Wiring
The remote devices described below require low voltage wiring. All wiring to
and from these remote input devices to the UCM must be made with
shielded, twisted-pair conductors. Be sure to ground the shielding only at the
Clear Language Display. See Wiring Section for the recommended conductor
sizes.
Emergency Stop (Normal Trip)
The Clear Language Display provides auxiliary control for a customer
specified/ installed latching tripout. When this customer-furnished remote
contact (5K18) is provided, the chiller will run normally when the contact is
closed. When the contact opens, the unit will trip off on a manually resettable
diagnostic. This condition requires manual reset at the chiller switch on the
front of the Clear Language Display.
To connect, first remove the jumper located between terminals 3 and 4 of
1U1TB1 Connect low voltage leads 513 and 514 to those terminals. Refer to
the field diagrams which are shipped with the unit.
Silver or gold-plated contacts are recommended. These customer-furnished
contacts must be compatible with 12 VDC, 45 mA resistive load.
External Circuit Lockout — Circuit #1
The UCM provides for auxiliary control via a customer specified or installed
contact closure, for individual operation of Circuit #1. If the contact is closed,
the refrigerant circuit will not operate. The refrigerant circuit will run normally
when the contact is opened. This feature is used to restrict total chiller
operation, eg. during emergency generator operations.
External circuit lockout will only function if External Circuit Lockout (Service
Setting Menu) is enabled.
These customer-supplied contact closures must be compatible with 12 VDC,
45 mA resistive load. Silver or gold plated contacts are recommended.
To install, cut, strip and wire-nut existing wire loop #W7 on the P43 connector
of the 1U4 module to low voltage leads 45A and 45B. Connections are shown
in the field diagrams which are shipped with the unit.
External Circuit Lockout — Circuit #2
The UCM provides for auxiliary control via a customer specified or installed
contact closure, for individual operation of Circuit #2. If the contact is closed,
the refrigerant circuit will not operate. The refrigerant circuit will run normally
when the contact is opened. This feature is used to restrict total chiller
operation, eg. during emergency generator operations.
External circuit lockout will only function if External Circuit Lockout (Service
Setting Menu) is enabled.
These customer-supplied contact closures must be compatible with 12 VDC,
45 mA resistive load. Silver or gold plated contacts are recommended.
To install, cut, strip and wire-nut existing wire loop #4 on the P53 connector
of the 1U5 module to low voltage leads 46A and 46B. Connections are shown
in the field diagrams which are shipped with the unit.
Ice Making Option
Ice Machine Control (Operator Settings Menu) must be Enabled. The UCM
provides auxiliary control for a customer specified/installed contact closure
for ice making. When contact (5K20) is provided, the chiller will run normally
when the contact is open. Upon contact closure, the UCM will initiate an ice-
building mode, in which the unit runs fully loaded at all times. Ice-building
shall be terminated either by opening the contact or based on the entering
evaporator water temperature setting under Active Ice Termination Set-point
(Chiller Report Menu). The UCM will not permit the ice-building mode to be
Содержание RTAA-100
Страница 12: ...12 RTAA SVX01A EN Installation Mechanical Figure 4 RTAA Rigging and Lifting Weights Packaged Unit...
Страница 13: ...RTAA SVX01A EN 13 Installation Mechanical Figure 5 RTAA Rigging and Lifting Weights Remote Evaporator...
Страница 14: ...14 RTAA SVX01A EN Installation Mechanical Figure 6 RTAA Rigging and Lifting Weights Pump Package Aluminum Fins...
Страница 15: ...RTAA SVX01A EN 15 Installation Mechanical Figure 7 RTAA Rigging and Lifting Weights Pump Package Copper Fins...
Страница 18: ...18 RTAA SVX01A EN Installation Mechanical Figure 8 Dimensions and Clearances for RTAA Packaged Unit 70 125 Tons...
Страница 20: ...20 RTAA SVX01A EN Installation Mechanical Figure 10 Remote Evaporator Dimensions RTAA 70 125 Tons...
Страница 21: ...RTAA SVX01A EN 21 Installation Mechanical Figure 11 Remote Evaporator Dimensions RTAA 110 125 Tons...
Страница 25: ...RTAA SVX01A EN 25 Installation Mechanical Figure 14 Isolator Placement for RTAA with Remote Evaporator...
Страница 45: ...RTAA SVX01A EN 45 Installation Remote Evaporator Figure 24 Refrigerant Sensor Mounting and Wiring...
Страница 65: ...RTAA SVX01A EN 65 Installation Electrical Figure 31 Remote Display Panel Interconnecting Wiring...
Страница 110: ...110 RTAA SVX01A EN Start Up Procedures Figure 37 Unit Sequence of Operation...
Страница 143: ...RTAA SVX01A EN 143 Pump Package Figure 47 Pump Package Piping Schematic...
Страница 144: ...144 RTAA SVX01A EN Pump Package...
Страница 146: ...146 RTAA SVX01A EN 3327...
Страница 147: ...RTAA SVX01A EN 147...
Страница 148: ...148 RTAA SVX01A EN 3328...
Страница 149: ...RTAA SVX01A EN 149...
Страница 150: ...150 RTAA SVX01A EN 6516...
Страница 151: ...RTAA SVX01A EN 151...
Страница 152: ...152 RTAA SVX01A EN 3329...
Страница 153: ...RTAA SVX01A EN 153...
Страница 154: ...154 RTAA SVX01A EN 6472...
Страница 155: ...RTAA SVX01A EN 155...
Страница 156: ...RTAA SVX01A EN 156 3330...
Страница 157: ...157 RTAA SVX01A EN...
Страница 158: ...158 RTAA SVX01A EN 6046...
Страница 159: ...RTAA SVX01A EN 159...
Страница 160: ...160 RTAA SVX01A EN 3331...
Страница 161: ...RTAA SVX01A EN 161...
Страница 162: ...162 RTAA SVX01A EN 6519...
Страница 163: ...RTAA SVX01A EN 163...
Страница 164: ...164 RTAA SVX01A EN 6047...
Страница 165: ...RTAA SVX01A EN 165...
Страница 166: ...166 RTAA SVX01A EN 3325...
Страница 167: ...RTAA SVX01A EN 167...
Страница 168: ...168 RTAA SVX01A EN 6048...
Страница 169: ...RTAA SVX01A EN 169...
Страница 172: ...172 RTAA SVX01A EN 3326...
Страница 173: ...RTAA SVX01A EN 173...
Страница 174: ...174 RTAA SVX01A EN 6049...
Страница 175: ...RTAA SVX01A EN 175...
Страница 176: ...176 RTAA SVX01A EN 6463...
Страница 177: ......