4
General Information
Model Number Description
All Trane products are identified by a multiple-character
model number that precisely identifies a particular type of
unit. An explanation of the alphanumeric identification code
is provided below. Its use will enable the owner/operator, in-
stalling contractors, and service engineers to define the op-
eration, specific components, and other options for any spe-
cific unit.
When ordering replacement parts or requesting service, be
sure to refer to the specific model number, serial number,
and DL number (if applicable) stamped on the unit name-
plate.
Compressor Nameplate
The nameplate for the “Scroll” compressors are located on
the compressor lower housing.
Hazard Identification
WARNING
– Indicates a potentially hazardous
situation which, if not avoided, could result in death or
serious injury.
CAUTION
– Indicates a potentially hazardous
situation which, if not avoided, may result in minor or
moderate injury. It may also be used to alert against
unsafe practices.
CAUTION
– Indicates a situation that may result in
equipment or property-damage-only accidents.
Sample Model Number:
CGAF - C30 4 A A B 0 D etc.
Digit Number:
1,2,3,4 5,6,7 8 9 10 11 12 13 +
Digit 1,2 - Unit Function
Digit 9 - Heating Capacity
Digit 13, etc. Miscellaneous
CG = Cold Generator
A = Standard
A = Communications Interface (TCI)
B = No Unit Heat Tape (50 Hz Units Only)
Digit 3 - Unit Type
Digit 10 - Design Sequence
C = Compressor Current Sensing (CSM)
A = Air-Cooled Condenser
H = Brazed Plate Chiller
D = Non-Fused Unit-Mounted Disconnect
E = *Unit Isolators - Neoprene P/S
Digit 4 - Development Sequence Digit 11 - Leaving Water Setpoint
F = *Unit Isolators - Spring P/S
F = Sixth
A = 40 - 50 F w/o Ice Machine
G = Superheat / Subcooling
B = 30 - 39 F w/o Ice Machine
H = Hot Gas Bypass
Digit 5,6,7 - Nominal Capacity
D = 51 - 65 F w/o Ice Machine
J = Generic BAS Module 0-5 VDC Input, Binary O.P
C20 = 20 Tons
E = 20 - 29 F w/o Ice Machine
L = LonTalk© Communication Interface Module
C25 = 25 Tons
1 = 40 - 50 F w Ice Machine
K = Stock Unit
C30 = 30 Tons
2 = 30 - 39 F w Ice Machine
L = LonTalk© Communication Interface Module
C40 = 40 Tons
3 = 51 - 65 F w Ice Machine
M = *Remote Human Interface
C50 = 50 Tons
4 = 20 - 29 F w Ice Machine
N = Generic BAS Module 0-10 VDC Analog Output
C60 = 60 Tons
S = Special
P = Remote Setpoint Potentiometer P/S
Q = *Zone Sensor (Chilled Solution Reset) P/S
Digit 8 - Power Supply
S = Special
E = 200/60/3 P/S***
V = Copper Fin Condenser Coil
F = 230/60/3
W = **Electronic Low Ambient Dampers P/S
4 = 460/60/3 P/S***
Y = *Inter-Processor Comm Bridge (IPCB)
5 = 575/50/3
Digit 12 - Agency Approval
9 = Packed Stock Unit
9 = 380/50/3
0 = None
* = Field Installed Options
D = 415/50/3
1 = UL/CSA
** = Factory or Field Installed Option
S = Special
*** Available on Pack Stock Units
Unit Nameplate
One Mylar unit nameplate is located on the outside upper
right corner of the control panel door. It includes the unit
model number, serial number, electrical characteristics,
weight, refrigerant charge, as well as other pertinent unit
data. A small metal nameplate with the Model Number, Se-
rial Number, and Unit Weight is located just above the Mylar
nameplate, and a third nameplate is located on the inside of
the control panel door.
When ordering replacement parts or requesting service, be
sure to refer to the specific model number, serial number,
and DL number (if applicable) stamped on the unit name-
plate.
Evaporator Nameplate
The nameplate is located on the opposite side of the water
connections. The word “Nameplate” is stenciled on the in-
sulation above the nameplate. To view the nameplate, re-
move the tape over the area and spread the insulation.
Retape the insulation after viewing.
Echelon, LON, LONWORKS, LonBuilder, NodeBuilder, LonManager, LonTalk, LonUsers, Neuron, 3120, 3150, the Echelon logo, and the LonUsers logo are
trademarks of Echelon Corporation registered in the United States and other countries. LonLink, LonResponse, LonSupport, LonMaker, and LonPoint are
trademarks of Echelon Corporation.
Содержание IntelliPak CG-SVX02B-EN
Страница 10: ...10 General Information Module Mounting Locations Screw Hole...
Страница 12: ...12 Figure 1 Typical Installation Clearances for Single Multiple or Pit Applications...
Страница 13: ...13 Figure 2 C20 Ton Unit Dimensional Data Recommended Clearances...
Страница 14: ...14 Figure 2 C25 Ton Unit Dimensional Data Recommended Clearances...
Страница 15: ...15 Figure 2 C30 Ton Unit Dimensional Data Recommended Clearances...
Страница 16: ...16 Figure 2 C40 Ton Unit Dimensional Data Recommended Clearances...
Страница 17: ...17 Figure 2 C50 Ton Unit Dimensional Data Recommended Clearances...
Страница 18: ...18 Figure 2 C60 Ton Unit Dimensional Data Recommended Clearances...
Страница 35: ...35...
Страница 36: ...36 Figure 12B Typical GBAS 0 5 Volt Connections Diagram...
Страница 37: ...37...
Страница 38: ...38...
Страница 63: ...63...
Страница 64: ......