System Start-Up
Figure 15
Condenser Fan Locations
8. Open the Human Interface access door, located in the
unit control panel, and press the SERVICE MODE key to
display the first service screen. Refer to the latest edition
of the Trouble Shooting Guide for the SERVICE TEST
screens and programming instructions.
9. Program the following system components for operation
by scrolling through the displays;
20 through 30 Ton
Compressor 1A (On)
Compressor 1B (Off)
Condenser Fans (On)
Solution Pump (On)
40 through 60 Ton
Compressor 1A (On)
Compressor 1B (Off)
Compressor 2A (Off)
Compressor 2B (Off)
Condenser Fans (On)
Solution Pump (On)
Note: Pump operation is dependent upon proper
solution flow proving switch operation. Please see
section titled "Loss-Of-Flow Protection" under
General Information for details.
10. Attach a set of service gauges onto the suction and dis-
charge gauge ports for each circuit. Refer to Figure 16
for the various compressor locations.
11. Once the configuration for the components is complete,
press the NEXT key until the LCD displays the “Start test
in __Sec.” screen. Press the + key to designate the de-
lay before the test is to start. This service test will begin
after the TEST START key is pressed and the delay des-
ignated in this step has elapsed. Press the ENTER key
to confirm this choice.
Содержание IntelliPak CG-SVX02B-EN
Страница 10: ...10 General Information Module Mounting Locations Screw Hole...
Страница 12: ...12 Figure 1 Typical Installation Clearances for Single Multiple or Pit Applications...
Страница 13: ...13 Figure 2 C20 Ton Unit Dimensional Data Recommended Clearances...
Страница 14: ...14 Figure 2 C25 Ton Unit Dimensional Data Recommended Clearances...
Страница 15: ...15 Figure 2 C30 Ton Unit Dimensional Data Recommended Clearances...
Страница 16: ...16 Figure 2 C40 Ton Unit Dimensional Data Recommended Clearances...
Страница 17: ...17 Figure 2 C50 Ton Unit Dimensional Data Recommended Clearances...
Страница 18: ...18 Figure 2 C60 Ton Unit Dimensional Data Recommended Clearances...
Страница 35: ...35...
Страница 36: ...36 Figure 12B Typical GBAS 0 5 Volt Connections Diagram...
Страница 37: ...37...
Страница 38: ...38...
Страница 63: ...63...
Страница 64: ......